Prestige SOLO 110 and EXCELLENCE

Natural to LP Conversion

6

3. Press  the 

RIGHT

button  to  highlight  the

Manual Operation icon

then press the 

OK

button.

4.  Press  the 

OK

button  while  the  FAN  icon  is

highlighted  to  manually  fire  the  burner  and

power the CH circulator.

An adequate CH load must be present to dissi-

pate the heat generated during the combustion

test.  If an adequate CH load is not available, an

indirect water heater can be used to dissipate the

heat by creating a DHW call which will enable

the DHW circulator.

5.  Press the 

RIGHT

button to adjust the firing rate

to 100% (high fire).  Hold down the  

RIGHT

button to rapidly increase the firing rate.

6. If  the  combustion  levels  during  high  fire  are

outside  the  recommended  combustion  settings

adjust the THROTTLE SCREW (see Fig. 6) as

follows:

Counter-clockwise  adjustment  of  the  THROT-

TLE SCREW at High Fire (100% firing rate):

O2 decreases and C02 increases

Clockwise  adjustment  of  the  THROTTLE

SCREW at High Fire (100% firing rate):

O2 increases and CO2 decreases

7. Once  the  combustion  level  is  set  at  high  fire,

manually place the boiler into low fire mode by

pressing the 

LEFT

button to adjust firing rate

down to 1% (low fire).

8. If the CO

combustion level at low fire is not

/-0.2 of the combustion level measured

at high fire, remove the offset cover screw and

adjust the plastic OFFSET SCREW (see Fig. 6)

using a T-40 Torx wrench as follows:

Counter-clockwise  adjustment  of  OFFSET

SCREW at Low Fire (1% firing rate):

O2 increases and CO2 decreases

Clockwise adjustment  of OFFSET SCREW at

Low Fire (1% firing rate):

O2 decreases and CO2 increases

9. Press the 

OK

button while the fan icon is high-

lighted to shutdown the burner.

10. Press the 

DOWN

button to highlight the home

screen icon

then press 

OK 

to return to the

home screen.

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

NOTICE

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

Manual Operation

Released

Off

Off

Off

CH

CH1

FAN

DHW

SYS

CH2

Содержание PSRKIT65

Страница 1: ...lade Putty Knife Indicates a potentially hazardous situation which if ignored can result in serious injury or substantial property damage For your safety turn off electrical power supply at service panel and allow unit to cool before proceeding Failure to do so can cause severe personal injury or death Indicates special instructions on installa tion operation or maintenance which are important to ...

Страница 2: ...tion cable from the igniter MCBA and remove the ground wire at the igniter To ease the removal of the burner assembly remove the top jacket access panel 10 Disconnect the wiring harness connectors from the blower and remove the blower retaining screws Remove the blower with venturi and gas valve from the unit 11 Remove the 10 mm nuts and remove the burn er mounting plate assembly from the heat exc...

Страница 3: ...o the venturi using the three T 25 Torx screws Ensure the gas valve is orientated with the venturi correctly 18 Use the included alignment tool to install the new combustion chamber insulation in the heat exchanger Insert the alignment tool into the igniter opening as shown in Fig 4 Install the new combustion chamber insula tion in the heat exchanger so that the align ment tool goes over the corre...

Страница 4: ...lure to check for gas leaks can cause severe personal injury death or substantial property damage 24 Re attach the ignition cable MCBA and the ground wire to the ignitor 25 Reattach the air inlet elbow to the venturi 26 Reposition the control panel 27 Replace the front jacket panel and secure with the thumb screw on the upper edge of the unit 28 Install the top jacket access panel 29 Turn power to...

Страница 5: ... The control panel will display a L followed by the current boiler temperature when placed into low fire test mode 4 If the CO2 combustion level at low fire is not within 0 2 of the combustion level measured at high fire remove the offset cover screw and adjust the plastic OFFSET SCREW using a T 40 Torx wrench see Fig 6 as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire O2 increas...

Страница 6: ...nt of the THROT TLE SCREW at High Fire 100 firing rate O2 decreases and C02 increases Clockwise adjustment of the THROTTLE SCREW at High Fire 100 firing rate O2 increases and CO2 decreases 7 Once the combustion level is set at high fire manually place the boiler into low fire mode by pressing the LEFT button to adjust firing rate down to 1 low fire 8 If the CO2 combustion level at low fire is not ...

Страница 7: ...h for latest recommendations 2 Wear long sleeved loose fitting clothing gloves and eyes protection 3 Assure adequate ventilation 4 Wash with soap and water after contact 5 Wash potentially contaminated clothes sepa rately from other laundry and rinse washing machine thoroughly 6 Discard used insulation in an air tight plastic bag Niosh Stated First Aid Eye Skin Immediately irrigate Breathing Clean...

Отзывы: