background image

Prestige SOLO 399

Burner Mounting Plate Kit

Instructions:

1. Turn power to the unit “OFF” and allow unit to

cool.

2. Shut off gas supply to the inlet of the unit at the

main manual shutoff valve to the unit.

3. Remove  the  front  panel  of  the  Prestige  by

removing the thumb screw on the upper edge of

the unit.  Lift the panel up and pull forward to

remove the front panel from the unit.

4. Remove  the  retaining  screw  from  the  control

panel.  Open the display panel cover and swing

the control panel out (MCBA).

5. Depress the retaining clips and tilt the control

panel down (TriMax).

6. Remove  the  air  inlet  elbow  from  the  venturi

using a twisting motion.

7. Disconnect  the  gas  supply  piping  inside  the

Prestige  enclosure  at  the  brass  union  located

just below the gas valve.

8. Disconnect wiring from gas valve.

9. Disconnect  the  ignition  cable  from  the  igniter

(MCBA),  and  remove  the  ground  wire  at  the

igniter.

To ease the removal of the burner assembly,

remove the top jacket access panel.

10. Disconnect the wiring harness connectors from

the  blower  and  remove  the  blower  retaining

nuts. Remove the blower with venturi and gas

valve from the unit.

11. Remove the 10 mm  nuts and remove the burn-

er  mounting  plate  assembly  from  the  heat

exchanger body.

12. Remove  the  combustion  chamber  insulation

from  the  heat  exchanger.  See  WARNING  on

page 7.

13. Remove the Phillips head screws attaching the

burner  head  to  the  burner  mounting  plate.

Inspect  the  burner  head  for  deterioration.

Replace if necessary.

For the reassembly process do not use adhe-

sives on ANY gasket surface.

14. Install the new sight glass assembly on the new

burner mounting plate.

15. With the new gasket in place attach the burner

head to the new burner mounting plate , as shown

in Fig. 2.

16. Use the included alignment tool to install the

new combustion chamber insulation in the heat

exchanger.
- Insert  the  alignment  tool  into  the  igniter

opening  as shown in Fig. 3.

- Install the new combustion chamber insula-

tion in the heat exchanger so that the align-

ment  tool  goes  over  the  correct  heat

exchanger stud as shown in Fig. 4.

- Remove the alignment tool.

NOTICE

NOTICE

2

10 mm

Mounting

nuts

Ignitor with

 ground wire

Gas Piping

Union 

Combustion

Chamber Insulation

Fig. 1: Burner  Assembly

Содержание PSRKIT39

Страница 1: ...rdous situation which if ignored can result in serious injury or substantial property damage For your safety turn off electrical power supply at service panel and allow unit to cool before proceeding...

Страница 2: ...ors from the blower and remove the blower retaining nuts Remove the blower with venturi and gas valve from the unit 11 Remove the 10 mm nuts and remove the burn er mounting plate assembly from the hea...

Страница 3: ...g nuts are in place use a wrench to tighten using an alternating pattern until the gasket is slightly compressed See Table 2 page 7 for torque specifications 21 Re assemble the blower onto the burner...

Страница 4: ...is operating at optimum conditions The combustion testing and adjustments must be performed by a qualified installer service agency or the gas supplier All com bustion measurements must be perform wit...

Страница 5: ...wrench see Fig 5 as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire O2 increases and CO2 decreases Clockwise adjustment of OFFSET SCREW at Low Fire O2 decreases and CO2 increases 5 P...

Страница 6: ...mbustion level is set at high fire manually place the boiler into low fire mode by pressing the LEFT button to adjust firing rate down to 1 low fire 8 If the CO2 combustion level at low fire is not wi...

Страница 7: ...for latest recommendations 2 Wear long sleeved loose fitting clothing gloves and eyes protection 3 Assure adequate ventilation 4 Wash with soap and water after contact 5 Wash potentially contaminated...

Отзывы: