10
The unit can also be place into the
OFF
mode when the
unit is in normal operation without entering the PARA
mode. In the STBY mode press and hold for approxi-
mately 2 seconds the - button. The panel display should
flash a d followed by a display of
dOFF
.
This method of using the - button to place the
DWH application in the OFF mode only controls
the burner operation. If the current parameter
setting is set for continuous pump operation the
DHW circulator will continue operating in a con-
tinuous pump mode. To alter both DHW burner
and circulator function the parameter setting
must be revised in the PARA mode.
The parameter adjustment of Parameter 2 in the CODE
mode is accomplished by following the steps given in
Program Access Section on page 2 until the display
shows
2_
XX
.
Use the + or - to adjust to the revised set-
ting listed below and press STORE to save the setting.
Parameter Adjustments - ON Mode
The Prestige is in factory set to this mode. However, the
parameter adjustment to set the DHW operational option
to
ON
can be done either through the STBY mode dur-
ing normal operation or by entering into the CODE
mode.
When the unit is normal operation and in the STBY
mode, press MODE button once to enter PARA. Press
STEP button twice to Parameter 2. Press + or - button
to adjust to the revised setting listed below and press
STORE to save the setting.
The unit can also be placed into the
ON
mode when the
unit is in the OFF mode operation without entering the
PARA mode. In the STBY mode press and hold for
approximately 2 seconds the - button. The panel display
should flash a d followed by a display of
d
XXX
. with
XXX indicating the current boiler temperature.
NOTICE
Returning the unit to the ON mode using the -
button will restore the burner function in
response to a “call for heat” request by the
IDWH. If the unit is in a continuous pump func-
tion the circulator will remain in that mode
unless the parameter setting is revised in the
PARA mode.
The parameter adjustment of Parameter 2 in the CODE
mode is done by following the steps given in Program
Access Section on page 2 until the display shows
2_
XX
. Use the + or - to adjust to the revised setting and
press STORE button to save the setting.
Parameter Adjustments - OFF + Continuous Pump
Mode
The parameter adjustment to set the DHW operational
function option to
OFF + Continuous Pump
can be
done either through the STBY mode during normal oper-
ation or by entering into the CODE mode.
When the unit is in normal operation and in the STBY
mode, press mode button once to enter PARA. Press
STEP button twice to Parameter 2. Press + or - button
to adjust to the revised setting listed below and press
STORE to save the setting.
The parameter adjustment of Parameter 2 in the CODE
mode is done by following the steps given in Program
Access Section on page 2 until the display shows
2_
XX
. Use the + or - to adjust to the revised setting and
press STORE to save the setting.
NOTICE
Parameter
Factory Setting
Revised Setting
2
2_01
2_00
Parameter
Factory Setting
Revised Setting
2
2_01
2_01
Parameter
Factory Setting
Revised Setting
2
2_01
2_02
Parameter
Factory Setting
Revised Setting
2
2_01
2_02