Startup Troubleshooting 
 
 
 

PROBLEM 

 

POSSIBLE CAUSE 

SOLUTION 

Temperature display not lit 
Unit will not start 

Check power supply to unit. 
Check circuit breaker or fuses 
Check 24 volt transformer 

Turn on or reset breaker. 
 
Check transformer/replace if 
required. 

Temperature display lit 
Unit will not start. 

Switch to “on” position. 
 
Water flow less than the 20 
gpm minimum required. 
 
 
 
 
 
Time delay and anticycle 
timers satisfied. 
 
 
 
Temperature set to low. 

Check on/off switch. 
 
Check that pump is on.  
Check that water is flowing 
through heater. 
Check any bypass valves that 
are installed. 
Check filtering system. 
Check pump and impeller. 
Check that pressure switch is 
closed. (needs 2 psi to close) 

Wait at least 8 min. without 
resetting on/ off switch or 
breakers.  

Set temperature setpoint above 
water temperature. 
Goldline control terminals “C” 
and “NO” close on call for 
heat. 

Pool water does not reach 
temperature setpoint. 

Heater runs only when pool 
timer is on. 
 
 
Outside air temperature is low.

Pool pump hold relay not 
wired in at installation. 
Electrician needs to wire pool 
pump hold relay per Figure 1. 
Install blanket on pool. 
 

Water dripping from bottom 
of unit. 

Water vapor will condense on 
the outside of the evaporator 
coil during normal operation. 
Leak at pipe connection 

No action

. This is normal. 

 
 
Repair as required. 

 
 
 

Содержание WCC100B

Страница 1: ...INSTALLATION OPERATING INSTRUCTIONS FOR AQUEFIER POOL HEATER Models WCC100B WCC100C WCC100L Trevor Martin Corp 4151 112th Terrace North Clearwater FL 33762 Bulletin PH 100 0702 ...

Страница 2: ...ture and starts adding heat if required The AQUEFIER Pool Heater will keep your pool pump running until it reaches your chosen temperature even if the pool timer turns off CAUTIONS DISCLAIMERS The AQUEFIER Pool Heater operates in conjunction with your pool equipment Improper installation can cause damage to both your Pool Heater your pool pump and filter piping Only skilled technicians with approp...

Страница 3: ...er temperatures to 100 degrees F c Before entering a pool or tub the user should measure the water temperature at several occupant locations using an accurate thermometer since the tolerance of the water temperature regulating devices may vary as much as or 5 degrees F d Alcohol drugs or medication should not be used before or during pool or tub use since their use may lead to unconsciousness with...

Страница 4: ...by the normal operation of the heat pump 3 Do not install the Pool Heater in an enclosed area such as a filter equipment room It is important to prevent the cool discharge air from being drawn back into the heat pump A beach location presents additional concerns Exposure to salt water spray and high winds will cause premature wear on the heat pump Salt and sand accumulation will clog up the heat p...

Страница 5: ...n Heat Pump instructions enclosed Bonding to Pool Steel Electrical corrosion known as electrolysis will occur if the heater is not bonded to the pool reinforcement steel Most local codes also require that the water pump be bonded Connect using a 8 gauge or larger solid copper wire to bond the cabinet to the pool reinforcement steel Power to the Pool Pump A standard feature on the Aquifier Pool Hea...

Страница 6: ...rect Replace the front panel on the cabinet POOL PIPING CONNECTIONS The Pool Heater is designed to handle the full flow from the pool pump No bypass is required if the water flow is in the 20 to 80 gallon per minute range The Pool Heater piping must be connected at a point in the pool piping loop after the pool water passes through the filter and before the chlorinator or chemical feeder Connectin...

Страница 7: ...b clockwise or counter clockwise or remove the clear plastic weather cover insert the 1 8 th inch hex wrench provided through the opening in the face of the digital temperature control and adjust the set point up or down as desired For more detailed instructions on the digital temperature refer to the Goldline SP 33 instructions enclosed After adjusting the temperature control check the water temp...

Страница 8: ...owed to start for an additional 4 minutes In most cases the heater will not start until at least 8 minutes has passed without resetting the on off switch or the breakers The heater will continue to heat the pool until the temperature setpoint has been satisfied PLEASE NOTE 1 It is important to remember that the pool heater will not run unless the pool pump is running 2 Water vapor will condense on...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ...er Side Pressure Drop Water Flow gal min Pressure Drop psig 20 0 23 30 0 46 40 0 74 50 1 06 60 1 42 70 1 86 80 2 32 Temperature Rise Across Heater Water Flow gal min Temperature Rise deg F 20 10 0 30 6 7 40 5 0 50 4 0 60 3 3 70 2 8 80 2 5 ...

Страница 14: ...s that are installed Check filtering system Check pump and impeller Check that pressure switch is closed needs 2 psi to close Wait at least 8 min without resetting on off switch or breakers Set temperature setpoint above water temperature Goldline control terminals C and NO close on call for heat Pool water does not reach temperature setpoint Heater runs only when pool timer is on Outside air temp...

Страница 15: ... any other liability in connection with this product except as may be authorized by an officer of Trevor Martin Corporation in a signed written document THERE ARE NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THAT APPLY TO THIS SALE LIMITATION OF REMEDY Trevor Martin Corporation will replace or repair at its option any product or component found to be defective durin...

Страница 16: ......

Отзывы: