RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014 3
Installation Instructions
RD-IQL
6
Configure IQLVAV/IQL+ for use with RD
7
Configure IQLVAV link (IQLVAV only)
3 INSTALLATION
(continued)
J5
R
D
I
5
A
S
Set link J5
Check link J6
Note that a PIN may be required to make changes. If
the PIN has been forgotten the users should contact
their supplier (installers contact Trend Technical
Support) quoting the generator number and neuron
id (both from Address module) whereupon a default PIN will
be supplied. This will only work for three attempts at entering
the PIN. After the default PIN is entered a new PIN should be
set up and remembered.
SET v5.1 IQLTool2
See IQLTool2
See PowerTool Manual (TE200163)
See Wupdn Manual (TE200162)
Connect Trend Tool for Text Communications
Configure parameters
The following parameters
must
be set up (their configuration is facilitated by IQLTool2 ‘Configure for RD-IQL’ feature):
Local Space Temp Type S9(Y=6) (use RD)
- IQL11+, 13+, 15+, IQLVAV
Local SP Adjust Type S10(Y=6) (use RD)
- IQL11+, 13+, 15+, IQLVAV
Local Fan Speed Type S11(Y=6) (use RD)
- IQL13+, 15+
These settings are facilitated by IQLTool2.
If it is required to use a separate temperature sensor, leave Local Space Temp Type at default, S9(Y=1).
If it is required to use a separate fan speed switch, leave Local Fan Speed Type at default, S11(Y=3).
The following parameters should be set up if they have been changed from default:
Note that these parameters are in the standard strategies; equivalent parameters may have to be changed in non-standard strategies
Window Mode W5(S=O)
(not window mode, default) - IQL11+
PIR Pb Select W6(S=O)
(Pushbutton selected, default) - IQL11+, 13+, 15+
Remote Fan Spd K7(V=4)
(auto, default) - IQL13+, 15+
The following command
must
be given:
R(z=1)
:This writes changes to permanent flash memory, and causes the IQL/IQLVAV to start using the new settings
IQLVAV Installation Instructions
e.g. IQLVAV/xxx ../VAV (TG200704)