2
RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014
RD-IQL
Installation Instructions
2
Mounting Requirements
(continued)
4
Remove Front Panel
5
Route Cable
3
Check IQL+, IQLVAV Controller Compatibility
3 INSTALLATION
(continued)
+45 °C
(+113 °F)
-10 °C
(+14 °F)
Operating Altitude:
<2000 m (6562’)
(maximum accuracy 0 to 40 °C, 32 to 104 °F)
H O
2
0 %RH
90%RH
IQLs must have standard strategies or standard item allocations as follows:
S9, S10, S1, S2, S3 (IQLVAV, IQL11+, 13+, 15+)
I9 (IQL11+, 13+, 15+), I12 (IQLVAV)
S11, S7 (IQL13+, 15+)
IQLVAV, IQL11+ can use RD/IQL/K, /KOS
IQL13+, 15+ can use RD/IQL/K, /KOS, /KOSF
The RD’s potentiometer must be used (if potentiometer required); a direct connected potentiometer may not be used. A direct
connected temperature sensor may be used rather than the RD’s.
RD-IQL/K
precludes use of PIR/pushbutton inputs and (on IQLVAV only) alarm contact input. A separate fan speed switch may
be used (IQL13+, 15+).
RD-IQL/KOS
as
RD-IQL/K
except pushbutton is provided.
RD-IQL/KOSF
as
RD-IQL/KOS
except Fan speed switch is provided (for IQL13+, 15+). A separate Fan Speed switch may be
used (rather than the RD’s).
Compatible with IQLVAV, IQL11+, 13+, 15+ only