NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2  , 20-Sep-2012 3

Installation Instructions 

NBOX(B)/CNC2

4

Connect power

3.1  Installation - Mounting

 (continued)

DO NOT

sWITCH ON

Shrouded plug ki

t

e   N    l 

 

 

 

~

E    N    L

/230 

version (shrouded plug kit must be used)

Terminal size 0.5 to 2.5 

mm

2

 (20 to 14 AWG)

/24 

version

NBOX/CNC2/230 Consumption < = 7.5 VA

The 230V supply must include a dedicated 5A fuse complying 

with BS1362 and a suitably rated switch in close proximity and 

be clearly marked as the disconnecting device for the unit. A  

5A circuit breaker with high breaking capacity may be used 

as an alternative .

Mat-N-LoK 

to 

terminals 

adaptor 

(supplied)

This unit is protected to safety class 2.

The  earth  on  this  unit  is  NOT  a  protective 

earth, but it is essential that an earth is fitted 

for functional reasons.

38

35

01

J

E

V4

2

24 Vdc

:  +24V         0v

24 Vac

: 24 Vac       0V

Earth 

(ground)

Note that for the UL 24 Vac the

input power connections must

be made using 18 AWG or

larger wire rated at least 90°C.

The 24V supply must include a suitably rated switch in close 

proximity and be clearly marked as the disconnecting device 

for the unit

NBOX/CNC2/24 Consumption < = 7.5 VA

TX

RX

OK

DTRB

DTRA

CTSB

CTSA

Earth/ground

the bus bar

TX

RX

OK

DTRB

DTRA

CTSB

CTSA

Earth/ground

the bus bar

a                                      b                                    c                             d                                     e

Содержание NBOX(B)/CNC2

Страница 1: ...y be impaired 1 Dimensions 3 Installation 3 1 Installation Mounting 1 Unpacking 2 Storing It is recommended that the installation should comply with the local electrical safety installation practices...

Страница 2: ...2 0 C 45 C 0 RH 95 RH Protection IP30 Operating Altitude 2000 m 6562 Must be installed in an enclosure rated to at least IP20 or equivalent For 24VAC only unit is UL rated as UL916 accessory to open e...

Страница 3: ...t A 5A circuit breaker with high breaking capacity may be used as an alternative Mat N LoK to terminals adaptor supplied This unit is protected to safety class 2 The earth on this unit is NOT a protec...

Страница 4: ...PC RS232 Port terminal size 0 5 to 2 5 mm2 additional terminals Connect Auxiliary Supply Output 7 3 1 Installation Mounting continued Cable 1k2 baud 4k8 baud 9k6 baud 19k2 baud No of Wires Belden 9182...

Страница 5: ...ue 2 20 Sep 2012 5 Installation Instructions NBOX B CNC2 2 Open Enclosure 1 Switch Off 9 Close Enclosure 3 1 Installation Mounting continued O I if fitted in ENCLS MBOX Other enclosure 3 Open Flap 3 2...

Страница 6: ...d A Baud B Baud A TX RX OK DTRB DTRA CTSB CTSA Network Baud Rate R1 move link to set baud rate e g 9k6 Baud B Baud A Baud B Baud A TX RX OK DTRB DTRA CTSB CTSA RS232 Port Baud Rate R2 move link to set...

Страница 7: ...og a power green red TX RX OK DTRB DTRA CTSB CTSA ON OFF ON OFF Note Batteries must be charged for 16 hours before they will support unit during mains failure NBOX B CNC2 NBOX B CNC2 TX RX OK DTRB DTR...

Страница 8: ...publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes Trend Control Systems Limited Albery House Springfield Road Ho...

Отзывы: