28
IQ23x Series Controllers Installation Instructions TG200539 Issue 2 , 23-Feb-2012
IQ23x
Installation Instructions
2
Upload IQ131+ Strategy
13 ReplaCIng an IQ131+ WITH an IQ233
Subject
Question
action Required
additional equipment
Fixing
Is it fixed in a small box (380 x 380 x 80
mm) using semicircular cutout fixings?
If YES, must drill new fixing holes
Is panel depth greater than 93 mm?
If not, can this be modified?
Power
Is mains supply capable of supplying
60 VA?
If not, increase power supply
External 2DP
Is an external 2 line display panel
fitted?
If YES must fit IQ233 with KIT/2xx/
RDS
KIT/2xx/RDS
Internal 2DP
Is internal 2 line display panel fitted?
If YES must use IQ233/DP/
IQ233/DP/..option
Extenal NDP
Is external NDP connected?
If YES use cable CABLE/EJ104029
for signal and power
CABLE/EJ104029
Local
Supervisor
Is local supervisor connected either
permanently or from time to time?
If YES replace complete cable with
new cable CABLE/EJ101442
CABLE/EJ101422
Auxiliary Supply Are the auxiliary supply terminals
used?
If YES connect to IQ233 auxiliary
supply terminals by 2 way
extension cable
2 way extension cable in KIT/
IQ23x/UPGRADE
Link Headers
Are link headers used?
If YES identify link headers below
LK/5V
Use LKE/5V
LKE/5V
LK/15V
Use LKE/15V
LKE/15V
LK/10mA
Use LKE/10mA
LKE/10mA
Internal Node
Is an internal node fitted?
If YES and node is CNC used to
connect local supervisor or NDP
to network, discard board, else if
YES, check below
Is the node based on the TMN board
(CNC2, PNC2, INC2, TMN, since
1999)?
Use TMN type board plate
TMN type board plate in KIT/
NODE/IQ23x
Is the node an older board (CNC, PNC,
INC,before 1999, and ANC, AND,
ENC, XN28, XNC+, MNC, LINC)?
Use pre-TMN type board plate
pre-TMN type board plate in
KIT/NODE/IQ23x
Is node CNC, CNC2, PNC, PNC2?
Use EJ100179A001 10 pin in line
socket (Molex) to 25 way female
D cable to connect to printer or
device
EJ100179A001 in KIT/NODE/
IQ23x
Is node TMNE?
Use EJ103817 10 pin in line socket
(Molex) to 25 way male D cable to
connect to modem
EJ103817 in KIT/NODE/
IQ23x
Is node ANC, AND, XN28?
Use 78-0903/1 10 pin in line socket
(Stocko) to 25 way male D cable to
connect to modem
78/0903/1 in KIT/NODE/
IQ23x
Internal Sensor Is internal sensor used in internal
digital mode?
If YES set bit 506,1
Fast Sequenced
Digital Inputs
Is a fast sequenced digital input in
input channel range 17 to 20 used?
If YES rewire inputs and change
strategy to move fast sequenced
digital inputs to channels 1 to 4
1
Survey Unit
WupDn Manual TE200162
PowerTool Manual TE200163
OR
9 ‘D type’
Female
Cable/58-0750
5 in line Stocko
Female
IQ131+
WupDn or
PowerTool
IQ131+
X.IQF
CABLE/78-1172
25 way ‘D type’ Female