Installation Guide
V1.0 04/21
P. 25 of 30
FIG.25:
100Wx3 W
iring Details
—
ProPoint Vista fixtures ship with two
cable whips: One cable whip for power
input, consisting of two wires plus a
ground, and one cable whip for
DMX512 RDM input/output.
—
No more than (32) fixtures on a single
DMX512 link, max 300m total (source to last fixture).
—
Data cabling from DMX source to first
fixture and between subsequent
ProPoint Vista fixtures shall be Cat5e
UTP or higher (stranded type only) or
other cable type suitable for DMX
communication. Consult DMX
standard for additional guidance.
signal r
—
Each DMX512 link must be
properly terminated to prevent
eflections.
General Notes
—
All data cabling must adhere to ANSI E1.11-2008 (R2013) – Entertainment Technology – USITT DMX512-A, Asynchronous Serial Digital Data Transmission Standard for Controlling Lighting Equipment and Accessories.
—
Fixture is RDM compatible.
—
Fixtures allow a universal input of 120V
AC
to 277V
AC
.
—
Data termination shall utilize cage clamp terminal blocks, or equivalent. Wire nuts are not permissible and will void warranty.
—
The method of line voltage termination, both for data and power, is at the discretion of the installing contractor, and/or engineer. Splicing and/or joining of cables must adhere to all applicable electrical codes.
—
Cables must be spliced/joined in a weatherproof enclosure/junction box, which is to be properly rated and provided by others.