Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert ( Figure 3 “q”).
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 3 must be met.
Minimum Clearances
k Sidewall
10.5" 267mm
l Side Facing (non-combustible)
5.5" 140mm
m Top Facing (non-combustible)
37" 940mm
n Mantel (combustible)
41" 1042mm
o Front Hearth
NOTE: Base of insert must be a minimum 1” above
combustible floor surfaces (carpet, wood, etc.). See
“Hearth Requirements” for further details.
18”* 458mm*
p Side Hearth
8" 204mm
q Front of Insert
36" 915mm
r Mantel Breastplate (max. 1” 26mm thick)
37” 940mm
s Mantel Column (max. 8” 204mm deep)
5.5" 140mm
x Extension Onto Hearth (from front edge of insert)
0" 0mm
* In the US, a 16” (407mm) hearth may be used if base of insert is 2” (51mm) above combustible floor
surfaces (carpet, wood, etc.). See “Hearth Requirements” for full details.
Figure 3
Combustible Top Facing
Side
Wall
Non-Combustible
Hearth
Facing
q
l
p
o
m
Combustible Mantel
n
Max. 1"
26mm
r
k
s
x