12
Stove Installation
(for qualified installers only)
Travis Industries
93508133
4 020509
Alcove Installation Requirements
Whenever the stove is placed in a location where the ceiling height is less than 7' tall, it is considered
an alcove installation. Because of the reduced height, the special installation requirements listed
below must be met.
•
Chimney connector and chimney must be one of the following types:
• DURAVENT model DVL with DURATEC chimney
• DURAVENT model DVL with DURA-PLUS chimney
• AMERI-TEC model DCC with model HS chimney
• SECURITY model DL with SECURITY model ASHT or S2100 chimney
• METAL-FAB model DW with TG chimney
• GSW Double Wall Chimney Connector with Super Chimney Twenty-One
• SELKIRK METALBESTOS model DS connector with model SSII chimney
• I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
• Standard Masonry Chimney with any one of the above listed connectors
Pendleton-45°
Pendleton-90°
Minimum Clearance
(See the illustration below)
Combustible
Alcove
Non-Combustible
Alcove
Combustible
Alcove
Non-Combustible
Alcove
A
Sidewall to stove
11"
6"
11"
6"
B
Backwall to stove
13"
5"
8 1/2"
2"
D
Connector to sidewall
19 1/2"
14 1/2
19 1/2"
14 1/2"
E
Connector to backwall
9"*
2 1/2"*
8 3/4"
2 1/4"
G
Maximum depth of alcove
48"
48"
48"
48"
H
Minimum width of alcove
45 3/4"
35 3/4"
45 3/4"
35 3/4"
J
Minimum height of alcove
84"
6" above stove top
84"
6" above stove top
•
Alcoves are classified as combustible or non-combustible. Non-combustible alcoves must have
walls and a ceiling that are 3 1/2" thick of a non-combustible material (brick, stone, or concrete).
This non-combustible material must be spaced and ventilated at least 1" off of all combustible
materials (walls, ceiling, etc.) to allow air to move around the non-combustible walls and ceiling.
All other alcoves are considered combustible. The clearances below must be met:
Non-combustible alcove
construction (on walls
and ceiling) - see the
explanation above.
AA
AA
AA
AA
3 1/2" thick non-
combustible
material
Combustible
materials
1" Min.
Ventilated
air space
Non-combustible
reinforcer
a
b
d
e
h
j
g