Installation
(for qualified installers only)
35
© Travis Industries
4140922
100-01410
Mantel Requirements
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the non-combustible facing) must fall within the shaded portion of the table.
Any material above the fireplace that protrudes more than 3/4” (19mm) from the non-combustible
facing is considered a mantel and must meet the mantel requirements.
Mantel Column Clearances
Combustible mantel columns (legs) that protrude more than ¾” (19mm) from the glass frame
require a 5” (127mm) clearance to the side of the fireplace.
Combustible mantel columns (legs) that protrude ¾” (19mm) or less from the glass frame must
meet the facing clearances (minimum 2-1/4” (57mm) clearance to the side of the glass frame).
Non-combustible mantel columns do not have a minimum clearance.
Maximum Mantel Depth (b)
Mantel
Height
Above
Base (a)
52-3/4" (1340mm)
0" (0mm)
1" (25mm)
2" (51mm)
8" (203mm)
7" (178mm)
6" (152mm)
5" (127mm)
4" (102mm)
3" (76mm)
9" (229mm)
10" (254mm)
11" (279mm)
12" (305mm)
51-3/4" (1314mm)
50-3/4" (1289mm)
49-3/4" (1264mm)
48-3/4" (1238mm)
47-3/4" (1213mm)
46-3/4" (1187mm)
53-3/4" (1365mm)
a
b
Mantel Column
(see clearances below)
Mantel Columns
45-3/4" (1213mm)
43-3/4" (1213mm)
44-3/4" (1213mm)