8
Installation (for qualified installers only)
© Travis Industries
4140808
100-01298
Fireplace Requirements
Insert must be placed within a code-conforming masonry fireplace or tested and listed factory-built
(metal) wood-burning fireplace. Repair any fireplace damage prior to installation.
Because the insert uses a circulation blower, clean the fireplace, smoke shelf, and chimney prior to
installation.
This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
Do not place insulation or any other material on top of the insert. This may block the upper accent
light ventilation, leading to premature bulb failure.
Fireplace Sizing
Minimum Height
24-1/4” (616mm)
Minimum Width
35” (889mm)
Minimum Depth
16-1/2” (420mm)
Hearth Depth (see
“Hearth Requirements”
on the following page
for full details)
12” (305mm)
The gas and electrical line should be installed prior
to installing the heater.
For tight fits (under 28”) see the section
“Removing the Vent Connector”
See “Leveling Bolts” for details on leveling the
heater.
h
Attach the “This fireplace has been altered…” plate to the fireplace (use two screws or other
suitable method). You may wish to place it in a location where it will be covered by the surround panels.
Fireplace Clearances to Gas Insert
Side of Insert to Inside of Fireplace
½” (13mm)
Back of Insert to Inside of Fireplace
½” (13mm)
Top of Insert to Inside of Fireplace
5/8” (18mm)
a
b
c
e
f
g
d
h
a
b
c
d
e
f
g