8 Installation 

 

(for qualified installers only)

 

Travis Industries 

4141209 

100-01378 

Massachusetts Requirements 

NOTE: The following requirements reference various Massachusetts and national codes not contained in this document. 

Requirements for the Commonwealth of Massachusetts 

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in 
part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent 
termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and 
porches, the following requirements shall be satisfied: 

Installation of Carbon Monoxide Detectors 

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall 
observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the 
gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard 
wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served 
by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the 
services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors. 
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired 
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall 
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day 
period, a battery operated carbon monoxide detector with an alarm shall be installed. 

Approved Carbon Monoxide Detectors 

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be 
ANSI/UL 2034 listed and IAS certified. 

Signage 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or 
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP 
CLEAR OF ALL OBSTRUCTIONS”. 

Inspection 

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation 
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the 
provisions of 248 CMR 5.08(2)(a)1 through 4. 

Exemptions 

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 
as adopted by the Board; and 
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the 
dwelling, building or structure used in whole or in part for residential purposes. 

MANUFACTURER REQUIREMENTS 

Gas Equipment Venting System Provided 

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or 
venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment 
and the venting system shall include: 
• Detailed instructions for the installation of the venting system design or the venting system components; and 
• A complete parts list for the venting system design or venting system. 

Gas Equipment Venting System NOT Provided 

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts 
for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the 
manufacturer: 
• The referenced “special venting system” instructions shall be included with the appliance or equipment installation 
instructions; and 
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a 
parts list and detailed installation instructions. 
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting 
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or 
equipment at the completion of the installation. 
See Gas Connection section for additional Commonwealth of Massachusetts requirements. 

Содержание 564 Cleanface

Страница 1: ...r HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this applian...

Страница 2: ...mpartment clean See installation and operating instructions accompanying appliance This appliance must be properly connected to a venting system in accordance with the manufacturer s installation inst...

Страница 3: ...sure 21 Gas Line Location 22 Converting Gas Line to the Left Side 22 Electrical Connection required 23 Accessing the Area Under the Burner 24 Vent Requirements 25 Vent Clearances 25 Altitude Considera...

Страница 4: ...nstalled in Manufactured Housing only after the home is site located All exhaust gases must be vented outside the structure of the living area Combustion air is drawn from outside the living area stru...

Страница 5: ...house how to shut gas off to the appliance and at the gas main shutoff valve The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to shut off A barrier des...

Страница 6: ...Per Hour 20 500 20 500 Heating capacity will vary with floor plan insulation and outside temperature Dimensions See Clearances and Framing Dimensions for details 31 75 807mm 38 25 972mm 28 625 728mm 4...

Страница 7: ...unded line Recommended Installation Procedure Frame the opening for the fireplace Make sure to allow for vent installation This fireplace is designed to accommodate 1 2 13mm drywall see Nailing Bracke...

Страница 8: ...uilding at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in pri...

Страница 9: ...diffuser when changing the vent configuration Converting the Fireplace to Top Vent Configuration Remove the 4 screws securing the outer flue assembly Place the screws and assembly aside NOTE Use a mag...

Страница 10: ...rear facing exhaust port with the same screws Verify the gasket on the intake cover plate is in place then attach it to the rear of the fireplace using the screws removed earlier Verify the gasket on...

Страница 11: ...ure to bend and secure the standoffs and drywall supports as shown below The two standoffs are shipped flat Bend both standoffs as shown below Remove the screw from the top of the fireplace and secure...

Страница 12: ...eater should be located out of traffic and away from furniture and draperies Fireplace must be placed so the vents below and above the glass do not become blocked Clearances The fireplace requires a 1...

Страница 13: ...vision The homeowner must understand that Travis Industries does not take responsibility for any negative impact to televisions placed near this fireplace Minimum Dimensions a Minimum Mantel Height ab...

Страница 14: ...evisions placed near this fireplace Minimum Dimensions a Minimum Buildout Height above Base of Fireplace 37 5 953mm with 8 203mm buildout depth b Minimum Fireplace TV Buildout Depth Minimum 8 203mm c...

Страница 15: ...s fireplace Minimum Dimensions a Minimum Buildout Height above Base of Fireplace 37 5 953mm with 8 203mm buildout depth b Minimum Buildout Depth Minimum 8 203mm c Fireplace Buildout Width 38 25 972mm...

Страница 16: ...on for qualified installers only Travis Industries 4141209 100 01378 Minimum Framing Dimensions 38 25 972mm 36 75 934mm MIn Enclosure 39 5 1004mm 19 125 486mm Flush Install 18 625 474mm Extended Tile...

Страница 17: ...is positioned to the rear Make sure to accommodate this dimension when configuring framing and determining the vent position gas line position etc Standard Facing drywall contacts side of fireplace Su...

Страница 18: ...aming dimensions shown in the illustration below NOTE all clearances still apply 7 5 191mm Approximate varies due to vent installation Minimum 0 5 13mm Clearance NOTE Most installations use 6 152mm Se...

Страница 19: ...is Industries 4141209 100 01378 Corner Installations Top Vent Configuration A typical 45 installation uses the framing dimensions shown in the illustration below NOTE all clearances still apply 14 25...

Страница 20: ...to each side of installed appliances see the illustration to the right All wiring connections to line power shall be in accordance with outdoor requirements of NECA NFPA 70 Warnings Regarding Tempered...

Страница 21: ...y pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPA For pressures under 1 2 psig kPA isolate the gas supply piping by closing the manual shutoff valve Leak test all gas l...

Страница 22: ...alve 3 4 wrench Gas line is located inside the fireplace on the right side 2 Remove the screw that holds the shutoff valve plate in place 1 4 nutdriver Remove the shutoff valve plate 3 Remove the cove...

Страница 23: ...er is shut off prior to working on any electrical lines The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Ele...

Страница 24: ...78 Accessing the Area Under the Burner The lower panel may be removed to access components This is required when relocating the electrical or gas inlet location or installing the LP regulator a Loosen...

Страница 25: ...uired 1 25mm clearance is met Vent Clearances The vent must maintain the required clearance to combustible materials to prevent a fire Do not fill air spaces with insulation Before 48 1219mm Rise Afte...

Страница 26: ...clearance Always use the high wind cap or high wind sconce cap part 58DVA HSCH or 46DVA HSCH Installation instructions for Simpson Dura Vent may be found at www duravent com Vent Installation Slide t...

Страница 27: ...able vent configurations detail the correct vent restrictor positions Exhaust Restrictor Adjustment If the diffuser is required to be in position 2 you may wish to adjust the diffuser while the exhaus...

Страница 28: ...y Travis Industries 4141209 100 01378 Intake Restrictor Adjustment Loosen the two screws holding the intake restrictor in place 1 4 Socket Slide the restrictor down to the lower position and tighten t...

Страница 29: ...2 is flattened See the directions below to change the diffuser to position 2 Back Wall of Firebox Firebox Roof Remove the exhaust restrictor 1 4 Nutdriver Remove the diffuser 1 4 Nutdriver Secure the...

Страница 30: ...ermine maximum vent 3 feet 915mm 0 feet mm 0 feet mm 4 max 610mm Exhaust Restrictor Remove the exhaust restrictor and replace the screws Intake Restrictor 1 stock Diffuser Position 1 stock Vent with N...

Страница 31: ...1 5 m 10 feet 3 m 5 feet 1 5 m 10 feet 3 m 0 feet 15 feet 4 5 m 20 max 6 m 10 feet 3 m 15 feet 4 5 m 15 feet 4 5 m 20 max 6 m 10 feet 3 m 15 feet 4 5 m 22 max 6 7 m 22 max 6 7 m Exhaust Restrictor 5...

Страница 32: ...3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 40 max 12m Exhaust Restrictor 5 Intake Restrictor 2 Diffuser Position 2 25 feet 7 5m 30 feet 9m...

Страница 33: ...20 feet 6m 20 feet 6m 5 feet 1 5m 10 feet 3m 5 feet 1 5m 10 feet 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 21 max 6 4m 21 max 6 4m Exhaus...

Страница 34: ...10 feet 3m 5 feet 1 5m 10 feet 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 40 max 12m Exhaust Restrictor 5 Intake Restrictor 2 Diffuser Posi...

Страница 35: ...of the gas supplier G Minimum 48 1219mm clearance from any adjacent building H Minimum 84 2134mm clearance above any grade when adjacent to public walkways or driveways NOTE may not be used over a wal...

Страница 36: ...7mm above the baseplate this area must remain open for screen and glass removal If installed near carpet or other combustible flooring the fireplace must be raised so the base of the unit is above the...

Страница 37: ...he glass frame It is typically removed if the front of the fireplace is left exposed If using tile or other non combustible facing over the front of the fireplace the tile stop is left in place to hel...

Страница 38: ...rimeter of the glass opening see c below Typical installations use 12 305mm or greater of non combustible facing around the perimeter of the glass opening Do not install facing over the ledge to the g...

Страница 39: ...e mantel requirements Steps for Finalizing the Installation 1 Remove the glass see page 43 Combustible mantel columns legs must be placed to the side of the fireplace face Non combustible mantel colum...

Страница 40: ...are in place NOTE Take care to not touch the bulb with your fingers use a cloth or paper towel 4 Install the four AA batteries see illustration below The AA batteries act as a power backup in case th...

Страница 41: ...ce instructions refer to the Owner s Manual part 100 01379 ACID WASH WARNING Before installing the faceplate make sure any masonry that has been treated with acid wash has been properly neutralized th...

Страница 42: ...her at risk individuals If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance c b Remove the concealment cover Lift the barrier up pivot the t...

Страница 43: ...eplace below the concealment cover Open the four latches holding the glass frame in place start with the bottom two follow the directions shown to the right a Lift the glass frame up and pull it forwa...

Страница 44: ...Installation for qualified installers only Travis Industries 4141209 100 01378 Log Set Installation Log Set Overview When installed the logs should appear as shown below Rear Log Left Log Right Twig L...

Страница 45: ...only 45 Travis Industries 4141209 100 01378 Rear Log Installation Place the rear log on the grate and slide it all the way back until the log contacts the end brackets on the grate The rear log has a...

Страница 46: ...for qualified installers only Travis Industries 4141209 100 01378 Right Log Installation Note how the right side of the log rests on the burner but does not cover any burner holes The right log has a...

Страница 47: ...r qualified installers only 47 Travis Industries 4141209 100 01378 Left Log Installation The left log has a groove that fits over the grate Note how the right side of the log rests on the burner but d...

Страница 48: ...allation for qualified installers only Travis Industries 4141209 100 01378 Left Twig Installation This hole fits over the pin on the rear log The left twig should be positioned so the front edge conta...

Страница 49: ...ation for qualified installers only 49 Travis Industries 4141209 100 01378 Right Twig Installation The right twig has two holes for the pins on the rear and right log When in place the right twig will...

Страница 50: ...ool is placed on top of the burner to enhance the glow from the burner The rock wool works best when it is applied in a very thin porous layer The best method for applying the rock wool is to brush it...

Страница 51: ...tor Kit SKU 94400999 is required for converting this appliance to LP The kit contains the stepper motor regulator and torx wrench The burner orifices and burner gaskets are shipped with the appliance...

Страница 52: ...in so the orifice protrudes 15 16 24mm indicating full insertion d Look here for the orifice identification Apply thread sealant to the LP orifices prior to installation Use the chart below to identi...

Страница 53: ...e logs and embers Replace the glass 6 Remove the control panel to access the gas control valve The stepper motor adjustable regulator has an installation sheet included with it make sure to follow all...

Страница 54: ...Restore the fireplace to the correct configuration Remove the grate replace after fireback installation 1 4 Nutdriver Remove and discard the hearth plate Loosen this screw and slide the bracket up Pla...

Страница 55: ...ox Manual On Off Accent Light s 3 Amp Fuse Optional Blower s 3 Amp Fuse Appliance Ground Accessory Power Appliance Ground Green Orange Yellow Green White Blue IPI CPI JUMPER WIRE Blue Pink Power In TO...

Страница 56: ...llation 44 LP Conversion Instructions 51 Mantel Requirements 39 Rear Vent Configuration with Horizontal Termination no vertical rise 30 Rear Vent Configuration with Horizontal Termination with vertica...

Отзывы: