Installation Guide 

– AC Surge Protection  

   

1104-11-101-M Rev D 

 

transtector.com 

 

 

General Wiring Instructions

 

 

  The SPD is installed in parallel with the load.  

 

Kelvin or ‘V’ connections are recommended.  

 

Keep wires as short as possible (maximum length ≤0.5m) and free of any sharp bends or loops.  

  All conductors should be insulated stranded copper. The ground conductor should be greater 

than 16mm

2

 (#6 AWG) diameter. The power conductors should be greater than 6 mm

2

 (#10 

AWG) diameter. If Kelvin connections are used, the load capacity of the conductor must be 
sized according to the load.  

 

System Configurations

 

 

Determine the electrical voltage configuration and then install per the appropriate wiring illustrations. 
 

 

 

 

Figure 4. Kelvin Connections   

 

Figure 5. Parallel Connections 

 

Remote Annunciation

 

 
Electrically isolated Form C dry contacts provide remote monitoring capability. The removable plug 
accepts #16 - #30 AWG wire. The maximum continuous current rating for the remote indicator is 3A. 
Strip the wire 0.25”, and torque the terminal screw 0.75 ft-lb. 
 

 

 

Figure 6. Remote Contact Connections

 