Transition Networks
PS-DC-DUAL-5624T Power Supply Install Guide
33788 Rev. D
Page
7
of
18
Connectors and LEDs
AC Input
•
Connector: IEC C14
•
Fuse: 6.3A slo blo
•
Power On/Off switch
56VDC and 24VDC output: 6-Pin Terminal Block
•
Pin 1:
•
Pin 2: 24Vout-
•
Pin 3: Alarm Contacts 1
•
Pin 4: Alarm Contacts 2
•
Pin 5:
•
Pin 6: 56Vout-
LEDs
•
Power status
o
Green: OK
o
Yellow blink: Will cycle through if one or more events (alarms) occur with one of these Blink Rates:
1 blink per 3 seconds: Fan locked (no tach)
2 blinks per 3 seconds: Fan less than 30% PWM (Pulse Width Modulation) setting
3 blinks per 3 seconds: 24VDC output out of spec
4 blinks per 3 seconds: Exceeding -25 Deg. C
5 blinks per 3 seconds: Exc75 Deg. C
If more than one alarm is set the LED will cycle through the Blink Rates one at a time, and then repeat until the alarm is
cleared.
Note
: These Blink Rates include a 3 second alarm delay to prevent triggering a false alarm when the fan ramps up or
down.