Features
Zone sensor technical features
Color of the wall sensor: light grey pantone #2C (equivalent to RAL 9002)
Room temperature sensor: 10 kohms at 25°C +/- 0.2°C
Thumbwheel : 1 kohms +/- 10%
Working temperature: -18°C to 65°C
Figures 9 and 10 show the wiring of the zone sensors.
Figure 9 - Zone sensor only
1 = Zone sensor
2 = Communication link (TH01 only)
3 = Factory-wired
4 = Occupancy window contact
5 = Zone sensor temperature sensor
6 = Communication BUS
7 = Return air sensor -
Ref 35168528-001
Note:
If a return air sensor is present, the internal
sensor of the wall sensor must be cut on jobsite.
CNT-SVX13B-E4
17
Figure 10 - Zone return air
sensor
Wiring to be done on job site
Wiring done in the factory