Factory-Mounted Unit Options
RT-SVX26K-EN
31
Powered and Unpowered
Convenience
Powered Convenience Outlet Powered
Option (FIYCOPO)
When the powered convenience outlet option is installed,
the unit will include a dedicated transformer located in the
evaporator section of the unit. Additionally, a service
receptacle disconnect switch will be provided on the side
wall of the evaporator section. The service receptacle
switch is shipped in the OFF position.
The powered outlet comes completely wired from the
factory except for 208 volt applications.
1.
For 208 volt applications, disconnect and tape the blue
230 volt wire.
2. Then connect the brown 208 volt wire.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged. Failure to
disconnect power and discharge capacitors before
servicing could result in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Figure 22. Wiring schematic 12½ through 25 ton options