PKGP-PRC001-EN
15
Performance
Data
(15 Ton)
*
Indicates both downflow and horizontal units.
Table PD-3 — Gross Cooling Capacities (MBh)
15 Ton Downflow and Horizontal Three Phase
WC*180B
Ambient Temperature ( F)
85
95
105
115
Enter.
CFM
Dry
Entering Wet Bulb (F)
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
162.3 130.3 184.5 103.3 194.1 71.1 150.5 124.1 176.5 99.0 190.3 68.4 137.5 117.3 163.6 93.0 185.5 65.5 124.8 110.8 149.4 94.8 176.1 61.2
5400
80
163.8 154.2 185.1 126.5 195.7 95.8 152.7 148.2 176.7 122.2 191.5 92.1 139.3 139.3 163.8 116.2 186.0 88.8 129.4 129.4 150.0 109.7 176.4 84.3
85
170.5 170.5 185.5 148.7 197.4 115.8 161.6 161.6 177.1 145.3 192.1 113.7 151.3 151.3 164.3 139.4 186.7 111.8 141.5 141.5 151.0 133.1 176.7 107.3
90
181.0 181.0 186.7 170.9 201.0 136.9 173.5 173.5 178.5 168.4 194.9 135.7 163.7 163.7 166.9 163.2 187.1 133.8 153.8 153.8 153.7 153.7 177.0 130.2
75
167.0 137.5 187.0 106.7 195.3 71.7 154.8 131.2 179.7 102.8 191.7 69.1 141.4 124.3 167.8 97.3 187.5 66.4 128.5 117.7 153.8 90.9 178.8 62.4
6000
80
169.2 163.7 187.6 131.0 197.2 98.1 156.0 156.0 180.0 128.0 193.2 95.1 145.5 145.5 168.0 122.6 188.3 91.8 135.3 135.3 154.1 116.1 179.2 87.6
85
177.5 177.5 188.5 154.8 199.6 118.6 168.9 168.9 180.6 152.9 194.1 116.7 158.3 158.3 168.8 147.9 188.7 116.2 148.1 148.1 155.5 141.6 179.6 112.5
90
186.6 186.6 190.1 178.4 202.6 140.1 180.0 180.0 182.7 177.5 197.3 140.3 171.1 171.1 171.0 171.0 189.9 139.5 161.1 161.1 161.2 161.2 180.0 136.8
75
170.8 144.2 188.9 110.1 196.2 72.6 158.6 137.9 182.2 106.4 192.7 70.2 144.9 131.0 171.3 101.3 188.8 67.3 131.8 124.4 157.2 95.0 180.7 63.4
6600
80
173.6 172.6 189.7 134.9 198.3 99.3 162.1 162.1 182.7 133.3 194.4 97.9 151.1 151.1 171.5 128.5 190.0 94.7 140.6 140.6 157.6 122.2 181.2 90.5
85
182.5 182.5 191.0 160.1 200.5 120.2 175.0 175.0 183.6 159.7 195.9 119.6 164.6 164.6 172.7 155.9 190.8 119.7 154.0 154.0 159.6 149.9 181.6 117.1
90
190.6 190.6 192.9 184.7 202.3 140.8 184.9 184.9 186.2 185.4 199.1 144.1 177.1 177.1 177.0 177.0 192.1 144.4 167.4 167.4 167.3 167.3 182.6 142.8
75
174.0 150.5 190.0 112.2 196.9 73.6 162.1 144.4 184.2 109.7 193.5 71.2 148.1 137.4 174.0 105.0 189.9 68.2 134.8 130.7 160.2 98.8 182.1 64.2
7200
80
176.7 176.7 191.4 138.3 199.1 100.2 167.6 167.6 184.8 137.8 195.7 99.2 156.3 156.3 174.3 134.1 190.7 97.2 145.4 145.4 160.6 128.0 182.9 93.4
85
186.4 186.4 192.9 164.7 201.5 121.7 179.6 179.6 186.0 165.5 197.7 122.4 170.1 170.1 175.9 163.3 192.4 122.8 159.4 159.4 163.2 157.7 183.5 121.0
90
193.8 193.8 195.1 190.1 203.3 143.0 188.6 188.6 188.5 188.5 200.6 147.4 181.9 181.9 181.7 181.7 193.9 148.7 172.6 172.6 172.5 172.5 184.6 148.2
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Содержание Voyager PKGP-PRC001-EN
Страница 1: ...PackagedHeatPumps Voyager 12 to 20T ons 60 Hz PKGP PRC001 EN September 2004 ...
Страница 34: ...34 PKGP PRC001 EN Typical Wiring 12 20Tons ...
Страница 35: ...PKGP PRC001 EN 35 Typical Wiring 12 20Tons ...
Страница 36: ...36 PKGP PRC001 EN Typical Wiring 12 20Tons ...
Страница 37: ...PKGP PRC001 EN 37 Typical Wiring 12 20Tons ...