12
PKGP-PRC001-EN
(12½ Ton)
General
Data
*Indicates both downflow and horizontal units.
Table GD-1 — General Data
12½ Ton Downflow and Horizontal Units
WCD150B3, B4, BW
WCH150B3, B4, BW
Cooling Performance
1
Gross Cooling Capacity
152,00
152,000
EER
2
9.5
9.5
Nominal CFM / ARI Rated CFM
4,400 / 4,400
4,400 / 4,400
ARI Net Cooling Capacity
144,000
144,000
Integrated Part Load Value
3
9.9
9.9
System Power KW
15.16
15.16
Heating Performance
1
High Temp. Btuh Rating
135,000
132,000
System Power KW/COP
12.76/3.10
12.48/3.10
Low Temp. Btuh Rating
78,000
72,000
System Power KW/COP
10.88/2.1
10.55/2.0
HSPF (Btu/Watts-hr)
—
—
Compressor
No./Type
2/Scroll
2/Scroll
ARI Sound Rating
(BELS)
4
9.2
9.2
Outdoor Coil
— Type
Hi-Performance
Hi-Performance
Tube Size (in.) OD
.375
.375
Face Area (sq ft)
23.96
23.96
Rows/FPI
2/16
2/16
Refrigerant Control
Expansion Valve
Expansion Valve
Indoor Coil
— Type
Hi-Performance
Hi-Performance
Tube Size (in.)
.375
.375
Face Area (sq ft)
15.83
17.50
Rows/FPI
2/15
2/15
Refrigerant Control
Capillary Tube
Capillary Tube
Drain Connection No./Size (in.)
1/1.00 NPT
1/1.00 NPT
Outdoor Fan
— Type
Propeller
Propeller
No. Used/Diameter (in.)
2/26
2/26
Drive Type/No. Speeds
Direct/1
Direct/1
CFM
10,800
10,800
No. Motors/HP
2/.50
2/.50
Motor RPM
1,110
1,110
Indoor Fan
— Type
FC Centrifugal
FC Centrifugal
No. Used
1
1
Diameter x Width (in.)
15 x 15
15 x 15
Drive Type/No. Speeds
Belt/1
Belt/1
No. Motors
1
1
Motor HP (Standard/Oversized)
3.0/5.0
3.0/5.0
Motor RPM (Standard/Oversized)
1,740/3,450
1,740/3,450
Motor Frame Size (Standard/Oversized)
145T/145T
145T/145T
Filters
— Type Furnished
6
Throwaway
Throwaway
(No.) Size Recommended (in.)
(2) 20 x 20 x 2
(2) 20 x 20 x 2
(4) 20 x 25 x 2
(4) 20 x 25 x 2
Refrigerant Charge
(Lbs of R-22)
5
11.1/11.4 Circuit
11.5/11.8 Circuit
Notes:
1. Cooling Performance and Heating Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ASHRAE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filter also available.
Содержание Voyager PKGP-PRC001-EN
Страница 1: ...PackagedHeatPumps Voyager 12 to 20T ons 60 Hz PKGP PRC001 EN September 2004 ...
Страница 34: ...34 PKGP PRC001 EN Typical Wiring 12 20Tons ...
Страница 35: ...PKGP PRC001 EN 35 Typical Wiring 12 20Tons ...
Страница 36: ...36 PKGP PRC001 EN Typical Wiring 12 20Tons ...
Страница 37: ...PKGP PRC001 EN 37 Typical Wiring 12 20Tons ...