Trane VariTrane Скачать руководство пользователя страница 19

VAV-SVX03A-EN

19

3. Slowly rotate the zone sensor until the

amber LED on the circuit board
illuminates. Voltage at terminal TP2 to
ground should be approximately
3.2 volts DC.

4. Continue rotating the zone sensor until

the first stage of heat energizes. This
can be determined by voltage across
terminals J7 to J9. At this point, the
green LED on the circuit board should
illuminate. Voltage at terminal TP2 to
ground should be 3.9 volts DC or
higher. R68 should be in control.

5. Now adjust the zone sensor so that the

output voltage at terminals 2 and 3 is
6.0 volts DC, +.01 volts DC, -.01
volts DC.

6. Compare the actual zone sensor to the

indicated setpoint on the dial of the
zone sensor. If the two readings are
within 3°F of each other, then the zone
sensor is within standard calibration
tolerance. Calibration procedures are
described in the Calibration Section in
this manual.

7. Note position of R69. Rotate

potentiometer R69 clockwise and
counter-clockwise while watching the
amber and green LED’s to make sure
that the control is now with minimum
potentiometer R69.

8. Return R69 to its original position.

Electronic Zone Sensor
Check

Note: The following checkout procedures
will be used when power is applied to
the electronic zone sensor.

1. Room temperature must be between

65°F and 80°F. Make sure also that
placement of the zone sensor is
satisfactory. It should not be located in
direct sunlight, on cold or hot wall
surfaces, etc. A zone sensor or other
accurate temperature measuring
device should be installed next to the
zone sensor. It is preferable to mount
the temperature sensing element
under the zone sensor cover next to
the thermistor of the zone sensor. (the
Thermistor is a small electronic
temperature sensing device
imbedded in a glob of silicone
cement.)

2. Remove the zone sensor cover.
3. Attach a volt meter to terminals 2 (+)

and terminal 3 (-).

4. Record temperature in zone. It should

be between 65°F and 80°F.

Troubleshooting

5. Check the voltage a terminals 2 (+)

and terminal 3 (-). If the zone
temperature and the zone sensor
setpoint are at equilibrium, the voltage
at this point should be 6.00-volts DC.

6. Rotate the zone sensor to the full-

heating position. Allow five minutes for
the zone sensor to equalize setpoint.
The voltage on terminals 2 and 3
should drop to 5.5-volts DC or less.

7. Rotate the zone sensor to the full

cooling position.  The voltage on
terminals 2 and 3 should rise to
6.3-volts DC or higher.

Jack Numbering Designations
for Analog Control Boards

Jack

Function

J1

Motor

J3

Transducer

J9

Stage 1 Contact

J10

Stage 2 Contact

J11

Stage 3 Contact

J15

Drive MAX (constant volume)

J18

Auto Dual Minimum

J19

Output Override

TB1

Field Connections: Power and Zone
Sensor

Содержание VariTrane

Страница 1: ...on Owner Programming VariT rane Analog ElectronicControls VAV SVX03A EN November 2001 For use with Single Duct Cooling Reheat Units Parallel Series Fan Powered Units Low Height Parallel Series Fan Pow...

Страница 2: ...VAV SVX03A EN 2001 American Standard Inc All rights reserved...

Страница 3: ...l Minimum 10 Calibration Transducer Operation 11 NullVoltage 11 Procedure for Maximum and Minimum Calibration 11 Set Maximum Flow 11 Set Minimum Flow 12 No Dual Minimum 12 Auto Dual Minimum 12 Balanci...

Страница 4: ...n transit damage must be filed immediately with the delivery carrier For re heat units check the coil fins and make sure the coils are not damaged Locate and verify that the correct zone sensors are w...

Страница 5: ...ntain the desired temperature the re heat will be activated to increase the temperature of the discharge air On a parallel unit theVariTrane air damper delivers primary cooling air to the unit outlet...

Страница 6: ...6 VAV SVX03A EN Figure 2 Typical Fan Powered Units Unit Information VSCF VSWF VSEF VPCF VPWF VPEF...

Страница 7: ...all unit sizes 3 A minimum setting of zero is permissible except forVCEF units Analog Controls Electronic Controls Installation Check the wiring on the unit with the wiring diagram and wiring informat...

Страница 8: ...changeable with DDC zone sensors The three wires required for the wall zone sensor to the terminal block are to be furnished and completed by the installer If local codes require enclosed conductors t...

Страница 9: ...ature is 0 5 F below the setpoint the damper begins to modulate to its minimum position supplying less cold air and more warm plenum air When the air damper is at minimum and zone temperature is still...

Страница 10: ...to the flow voltage Control Options Auto Dual Minimum The auto dual minimum enables the unit to change the minimum automati cally without an outside signal The minimum changes when the first stage re...

Страница 11: ...Rotate min B R69 full counter clockwise 3 With both of the transducer ports open to ambient 0 delta P read the output voltage atTP4 Ground is eitherTP3 TB1 2 orTB1 3 The value of the null transducer...

Страница 12: ...closed when minimum is desired Auto Dual Minimum Place jumper on J18 A to B The heating minimum is the minimum at which the damper is controlled to when the fan on a fan powered unit is activated or w...

Страница 13: ...ck the 12 volts DC power supply of the circuit card terminalsTB1 5 to TB1 3 Acceptable range 11 6 to 12 4 volts DC 3 Install the magnehelic gage to observe delta P When connecting to the test tees be...

Страница 14: ...at jack J3 5 Reheat stages or fan on fan powered units are connected at jacks J7 24 VAC J9 J10 and J11 6 Various options to cause changes to the operation of unit are input at jack J15 7 There are va...

Страница 15: ...rmistor will equal the voltage drop between terminal 2 and Zone Sensor terminal 3 With the voltages being equal the room temperature is considered satisfied and all output relays are de energized If t...

Страница 16: ...k leaving air temperature from air handling unit Coils do not engage on Faulty relay orTriac Check for voltage to heating coil and relay s Verify supply voltage matches coil voltage Call for heat Boar...

Страница 17: ...n the room setpoint is above the actual room temperature stages of heat will be energized if enabled 3 If the zone sensor does not operate at all check the wiring from the board to the sensor Referenc...

Страница 18: ...trol Refer to prior sections for step by step procedures 2 Remove all connections from J9 J10 and J11 In addition remove J19 if it is a series fan power unit 3 Set the zone sensor to the full cooling...

Страница 19: ...om temperature must be between 65 F and 80 F Make sure also that placement of the zone sensor is satisfactory It should not be located in direct sunlight on cold or hot wall surfaces etc A zone sensor...

Страница 20: ...VAV SVX03A EN File Number SL TD VAV 000 SBX03A EN 1101 Supersedes New Stocking Location La Crosse SinceTheTrane Company has a policy of continuous product and product data improvement it reserves the...

Отзывы: