Trane VariTrane Скачать руководство пользователя страница 18

18

VAV-SVX03A-EN

Troubleshooting

Fan Motor Check

To troubleshoot the fan motor, complete
the following procedure:

1. Disconnect the power, check all wiring

diagrams provided on the unit.

2. Turn the power back on. Operate the

zone sensor to see if the proper
voltage is being supplied to the motor
relay. If the motor does not start, check
the capacitor and fan motor.

3. Check the motor relay by attaching a

voltmeter across the 24-volt coil of the
relay. For parallel fan-powered,
operate the zone sensor to energize
the fan and confirm the voltage to the
relay is turned on. Check for supply
voltage between the common and hot
side of the relay.

4. Attach a Voltmeter to the white

common wire on the terminal block
and the blue, black or red wires from
the fan motor. If line voltage is present,
check for fan obstruction.

5. With the power off, spin the fan wheel.

If it does not run freely, check shaft
alignment or housing clearances.

Circuit Board Check

1. Remove the control box cover. Inspect

all wiring and compare with the label
on the control box cover.  The label
also indicates jumper connections.
Make sure that all wiring and jumpers
are connected exactly as shown on
the diagram.

2. Measure the voltage a terminals

TB1 –1 (+) and TB1 –2 (-) on the circuit
board. The voltage reading should be
24-volts AC +/- 10%.

3. Measure the voltage at terminal TB1-5

(+) and TB1-3 (-) on the circuit board.
Voltage reading should be 12-volts
DC + 10% tolerance.  This voltage is
the output power for the zone sensor.
If these voltage readings are not
shown, it could indicate a
defective board.

4. If 12-volts DC is present, rotate the

zone sensor thumbwheel and check
for voltage change across zone sensor
terminals 2 and 3.

5. Adjust the minimum fully counter-

clockwise and the maximum
fully clockwise.

6. Verify the amber and green lights

change when rotating the
thumbwheel.

7. If any step does not work,

replacement of the board may be
necessary. If all steps work, proceed
with further component checks.

Transducer Check

1. Disconnect the tubing to the flow

sensor, remove the low-pressure line
first, then the high side. Transducer
damage may result if procedure is
not followed.

2. Attach the voltmeter to terminals TP4

(+) and ground, B1-2 or 3, or TP3.
Voltage on these terminals should be
between .1- to .4-volts DC; the ideal is
.254 volts DC.

Triac Output Check

1. Make sure that the zone sensor

operation is correct and, if applicable,
which zone sensor is under control.
Refer to prior sections for step-by-step
procedures.

2. Remove all connections from J9, J10,

and J11. In addition, remove J19 if it is
a series fan-power unit.

3. Set the zone sensor to the full

cooling position.

4. Place a 500-1000 ohm resistor

between the connectors J7 and J9
and measure the voltage between
these points. It should be less than 10
volts AC.

5. Slowly increase the zone sensor

setting from full cooling to heating. At a
position on the zone sensor near room
temperature, Triac #1, which connects
J7 to J9 should close. Next, Triac 2,
which connects J7 to J10, should
energize and finally Triac 3, which
connects J7 to J11, should energize.
When the zone sensor is rotated to the
full heating position, a voltage check
should show that contact closures
between J7 and J9, J7 and J10, and
J7 and J11 have been made (closed).

6. If continuity is not present at all stages,

replace the board.

Auto Dual Minimum Check

A digital voltmeter will be required to
make the voltage checks described in
this procedure. Note the following
differences in labeling of adjustment
potentiometer described in the follow-
ing steps:

Circuit

Board

Label

R8

Null Voltage Calibration

R67

Max Flow

R68

Min Flow A

R69

Min Flow B

1. Refer to calibration setup steps 1

through 4. Make changes as described
in the following steps:

2. Rotate the zone sensor to the full cool

position. The green LED should be
illuminated on the circuit board and
voltage present at terminals J1-3 to
J1-1. The voltage at terminal TP2 to
ground should be 5.9 volts DC
or higher.

Hazardous Voltage!

Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout procedures
to ensure the power cannot be inadvert-
ently energized. Failure to disconnect
power before servicing could result in
death or serious injury.

WARNING

WARNING

3. Connect the voltmeter to terminals

TP1 (+) and ground. Voltage at these
terminals should be 4.78 to 4.82 volts
DC. If the voltage at these terminals is
lower or greater than the specified
tolerance, this could be the cause for
not obtaining correct minimum or
maximum flow.  This causes the
controller to not operate within the
specified minimum and maximum
values, even with the minimum
potentiometer fully counter-clockwise.
Adjust R8 for 4.8 volts DC.

4. Reconnect the air valve actuator and

drive to maximum position. Voltage
should increase on TP4 to TP3.

5. If voltage does not increase, verify

with a magnehelic that the delta P
is increasing.

6. Replace the transducer if delta P

increases and voltage does
not change.

Note: A faulty transducer will cause the
air damper to function improperly.

Содержание VariTrane

Страница 1: ...on Owner Programming VariT rane Analog ElectronicControls VAV SVX03A EN November 2001 For use with Single Duct Cooling Reheat Units Parallel Series Fan Powered Units Low Height Parallel Series Fan Pow...

Страница 2: ...VAV SVX03A EN 2001 American Standard Inc All rights reserved...

Страница 3: ...l Minimum 10 Calibration Transducer Operation 11 NullVoltage 11 Procedure for Maximum and Minimum Calibration 11 Set Maximum Flow 11 Set Minimum Flow 12 No Dual Minimum 12 Auto Dual Minimum 12 Balanci...

Страница 4: ...n transit damage must be filed immediately with the delivery carrier For re heat units check the coil fins and make sure the coils are not damaged Locate and verify that the correct zone sensors are w...

Страница 5: ...ntain the desired temperature the re heat will be activated to increase the temperature of the discharge air On a parallel unit theVariTrane air damper delivers primary cooling air to the unit outlet...

Страница 6: ...6 VAV SVX03A EN Figure 2 Typical Fan Powered Units Unit Information VSCF VSWF VSEF VPCF VPWF VPEF...

Страница 7: ...all unit sizes 3 A minimum setting of zero is permissible except forVCEF units Analog Controls Electronic Controls Installation Check the wiring on the unit with the wiring diagram and wiring informat...

Страница 8: ...changeable with DDC zone sensors The three wires required for the wall zone sensor to the terminal block are to be furnished and completed by the installer If local codes require enclosed conductors t...

Страница 9: ...ature is 0 5 F below the setpoint the damper begins to modulate to its minimum position supplying less cold air and more warm plenum air When the air damper is at minimum and zone temperature is still...

Страница 10: ...to the flow voltage Control Options Auto Dual Minimum The auto dual minimum enables the unit to change the minimum automati cally without an outside signal The minimum changes when the first stage re...

Страница 11: ...Rotate min B R69 full counter clockwise 3 With both of the transducer ports open to ambient 0 delta P read the output voltage atTP4 Ground is eitherTP3 TB1 2 orTB1 3 The value of the null transducer...

Страница 12: ...closed when minimum is desired Auto Dual Minimum Place jumper on J18 A to B The heating minimum is the minimum at which the damper is controlled to when the fan on a fan powered unit is activated or w...

Страница 13: ...ck the 12 volts DC power supply of the circuit card terminalsTB1 5 to TB1 3 Acceptable range 11 6 to 12 4 volts DC 3 Install the magnehelic gage to observe delta P When connecting to the test tees be...

Страница 14: ...at jack J3 5 Reheat stages or fan on fan powered units are connected at jacks J7 24 VAC J9 J10 and J11 6 Various options to cause changes to the operation of unit are input at jack J15 7 There are va...

Страница 15: ...rmistor will equal the voltage drop between terminal 2 and Zone Sensor terminal 3 With the voltages being equal the room temperature is considered satisfied and all output relays are de energized If t...

Страница 16: ...k leaving air temperature from air handling unit Coils do not engage on Faulty relay orTriac Check for voltage to heating coil and relay s Verify supply voltage matches coil voltage Call for heat Boar...

Страница 17: ...n the room setpoint is above the actual room temperature stages of heat will be energized if enabled 3 If the zone sensor does not operate at all check the wiring from the board to the sensor Referenc...

Страница 18: ...trol Refer to prior sections for step by step procedures 2 Remove all connections from J9 J10 and J11 In addition remove J19 if it is a series fan power unit 3 Set the zone sensor to the full cooling...

Страница 19: ...om temperature must be between 65 F and 80 F Make sure also that placement of the zone sensor is satisfactory It should not be located in direct sunlight on cold or hot wall surfaces etc A zone sensor...

Страница 20: ...VAV SVX03A EN File Number SL TD VAV 000 SBX03A EN 1101 Supersedes New Stocking Location La Crosse SinceTheTrane Company has a policy of continuous product and product data improvement it reserves the...

Отзывы: