VariTrac Installation 

19.  Press the View Button on the Home Screen. Three devices should display as shown. 
 
 

 

 

20.  Press the Home button

 to return to the home screen. 

 
21.  Make the following Setup changes to VariTrac: 

 

Hint: Press the ‘Advanced’ button to access the following options. 

 

π

 

Set current date and time 

π

 Change 

System Name:

 from “VariTrac CCP” to “Front Office Area” 

π

 Select 

HVAC Unit Type:

 as ‘Voyager Commercial CV’ 

π

 Change 

Discharge Heating Setpoint:

 to ‘100.0’ 

 
22.  Press ‘Advanced’, then ‘System setup and Status’, finally ‘System Status’. 
 
23.  Record the following and be prepared to explain the recorded values: 

 

π

 

HVAC Unit Comm: ___________________. 

π

 

HVAC Comm Status: __________________. 

π

 

Operating Mode: ____________________. 

π

 

Supply Air Temperature: ___________________. 

π

 

External Time Clock Input: ________________. 

 

24.  Press the Home button

 to return to the home screen. 

 
25.  Press the View Button on the Home Screen. 
 
26.  Select each zone and rename as follows: 
 

π

 

“Zone 1” rename to: = “Administration Area” 

π

 

“Zone 2” rename to: = “Lobby Area” 

π

 

“Zone 3” rename to: = “Sales Area”. 

 

 

03- VariTrac Installation Workshop.doc

  

3-9 

Содержание VariTrac

Страница 1: ...de VAV SVP01A EN Job Description A VariTrac III and Tracker 10 will be installed at B R Specialty Metals The VariTrac CCP is applied to the office area HVAC system This HVAC system consists of Voyager...

Страница 2: ...hrough 27 1 Set the address DIP switches on each of the UCM boards to addresses 1 2 and 3 2 Connect UCM Comm4 wiring to terminalsTB2 1 and TB2 2 TB2 3 and TB 2 4 on each UCM using the pre configured w...

Страница 3: ...______________________________ Question Will the comm link function even though the electrician swapped polarity at one of the Comm4 devices ______ Why or why not ________________________ 4 Install a...

Страница 4: ...b equipment and remove metal cover 7 Verify address DIP switches on the communicating sensor bypass UCM board are set to address 33 Note The communicating sensor assembly UCM address DIP switches are...

Страница 5: ...en the bypass damper actuator and communicating sensor bypass assembly if using the cable shipped with the bypass damper actuator unit ______________ Install VariTrac Central Control Panel Reference V...

Страница 6: ...rac termination board Note A dedicated 24 Vac 30VA Class 2 transformer is required to power the VariTrac Central Control Panel The ground wire TB2 3 is connected to the circuit breaker panel 12 Connec...

Страница 7: ...Comm4 link are correctly terminated at the VariTrac termination board 14 Install Main logic board onto the VariTrac termination board module 15 Install the VariTrac operator display module onto the m...

Страница 8: ...te when the operator displays the normal Home Screen 18 The VariTrac home screen should display as shown in the screen capture Note Calibration mode is active occurs after an initial start up sequence...

Страница 9: ...Setpoint to 100 0 22 Press Advanced then System setup and Status finally System Status 23 Record the following and be prepared to explain the recorded values HVAC Unit Comm ___________________ HVAC Co...

Страница 10: ...VariTrac Installation You have completed this workshop 03 VariTrac Installation Workshop doc 3 10...

Отзывы: