background image

VariTrac Installation 

Startup VariTrac and setup system from operator display 
 

 

Reference: VariTrac Installation Manual (VAV-SVN03A-EN), page 43 to 51

 

 

16.  Apply 24Vac power to VariTrac and UCMs.  
 

Question: What is the minimum configuration of VariTrac devices required for the CCP 
startup sequence to begin? ____________________________________________. 

 

17.  View the VariTrac operator display. The ‘System Initialization in Progress’ screen displays. 
 
 

Please Wait 

 

System initialization is in progress 

 

Initialization status: 90% complete 

 

 

 

Patience required:  VariTrac operator goes through an initialization routine which could 
last several minutes. Once initialization is complete when the operator displays the 
normal ‘Home Screen’. 

 

18. 

The VariTrac home screen should display as shown in the screen capture

 

 

 

 
 

Note: ‘Calibration mode is active’ occurs after an initial start-up sequence. In calibration, 
the CCP automatically prepares the VariTrac system for operation by disabling heating 
and cooling, closing the bypass damper, opening all zone dampers to their maximum 
position and starting the fan. Calibration re-indexes the zones and bypass damper and 
recalibrates the static pressure setpoint.  
 
Reference:
 VariTrac Installation Manual (VAV-SVN03A-EN), page 44 for an explanation 
of the VariTrac calibration sequence. 
 
Question
: Name 3 fault conditons that cause the home screen display to display: …… 
 

******Priority Shutdown Active******  

a. _________________________ 
b. _________________________ 

c. 

_________________________

 

03- VariTrac Installation Workshop.doc

  

3-8 

Содержание VariTrac

Страница 1: ...de VAV SVP01A EN Job Description A VariTrac III and Tracker 10 will be installed at B R Specialty Metals The VariTrac CCP is applied to the office area HVAC system This HVAC system consists of Voyager...

Страница 2: ...hrough 27 1 Set the address DIP switches on each of the UCM boards to addresses 1 2 and 3 2 Connect UCM Comm4 wiring to terminalsTB2 1 and TB2 2 TB2 3 and TB 2 4 on each UCM using the pre configured w...

Страница 3: ...______________________________ Question Will the comm link function even though the electrician swapped polarity at one of the Comm4 devices ______ Why or why not ________________________ 4 Install a...

Страница 4: ...b equipment and remove metal cover 7 Verify address DIP switches on the communicating sensor bypass UCM board are set to address 33 Note The communicating sensor assembly UCM address DIP switches are...

Страница 5: ...en the bypass damper actuator and communicating sensor bypass assembly if using the cable shipped with the bypass damper actuator unit ______________ Install VariTrac Central Control Panel Reference V...

Страница 6: ...rac termination board Note A dedicated 24 Vac 30VA Class 2 transformer is required to power the VariTrac Central Control Panel The ground wire TB2 3 is connected to the circuit breaker panel 12 Connec...

Страница 7: ...Comm4 link are correctly terminated at the VariTrac termination board 14 Install Main logic board onto the VariTrac termination board module 15 Install the VariTrac operator display module onto the m...

Страница 8: ...te when the operator displays the normal Home Screen 18 The VariTrac home screen should display as shown in the screen capture Note Calibration mode is active occurs after an initial start up sequence...

Страница 9: ...Setpoint to 100 0 22 Press Advanced then System setup and Status finally System Status 23 Record the following and be prepared to explain the recorded values HVAC Unit Comm ___________________ HVAC Co...

Страница 10: ...VariTrac Installation You have completed this workshop 03 VariTrac Installation Workshop doc 3 10...

Отзывы: