UNT-SVX07A-EN
39
Table I-ER-11. Force Flo single stage, low kW electric heat
unit size
voltage
# wires
kW
amps/ph
kW amps/ph
kW
amps/ph
02
208/60/1
2
0.75
3.7
1.5
7.3
240/60/1
2
1.0
4.2
2.0
8.4
277/60/1
2
1.0
3.7
2.0
7.3
03
208/60/1
2
2.25
10.9
240/60/1
2
3.0
12.5
277/60/1
2
3.0
10.9
208/60/3
3
2.25
6.3
240/60/3
3
3.0
7.3
480/60/3
4
3.0
3.7
04
208/60/1
2
2.25
10.9
240/60/1
2
3.0
12.5
277/60/1
2
3.0
10.9
208/60/3
3
2.25
6.3
240/60/3
3
3.0
7.3
480/60/3
4
3.0
3.7
06
208/60/1
2
2.25
10.9
3.3
15.9
240/60/1
2
3.0
12.5
4.5
18.8
277/60/1
2
3.0
10.9
4.5
16.3
208/60/3
3
2.25
6.3
3.3
9.2
240/60/3
3
3.0
7.3
4.5
10.9
480/60/3
4
3.0
3.7
4.5
5.5
08
208/60/1
2
2.25
10.9
3.3
15.9
4.5
21.7
240/60/1
2
3.0
12.5
4.5
18.8
6.0
25.0
277/60/1
2
3.0
10.9
4.5
16.3
6.0
21.7
208/60/3
3
2.25
6.3
3.3
9.2
4.5
12.5
240/60/3
3
3.0
7.3
4.5
10.9
6.0
14.5
480/60/3
4
3.0
3.7
4.5
5.5
6.0
7.3
10
208/60/1
2
2.25
10.9
3.3
15.9
5.7
27.5
240/60/1
2
3.0
12.5
4.5
18.8
7.5
31.3
277/60/1
2
3.0
10.9
4.5
16.3
7.5
27.1
208/60/3
3
2.25
6.3
3.3
9.2
5.7
15.9
240/60/3
3
3.0
7.3
4.5
10.9
7.5
18.1
480/60/3
4
3.0
3.7
4.5
5.5
7.5
9.1
12
208/60/1
2
2.25
10.9
3.3
15.9
6.6
31.8
240/60/1
2
3.0
12.5
4.5
18.8
9.0
37.5
277/60/1
2
3.0
10.9
4.5
16.3
9.0
32.5
208/60/3
3
2.25
6.3
3.3
9.2
6.6
18.4
240/60/3
3
3.0
7.3
4.5
10.9
9.0
21.7
480/60/3
4
3.0
3.7
4.5
5.5
9.0
10.9
Note: All data based on individual units. Electric heat will operate only with fan at high speed.
Table I-ER-10. Force Flo single-stage, max kW electric heat
unit
heater
heater
size
volts
hz
phase
wires
kW
amps/ph
208
1
2
2.25
10.9
240
1
2
3.0
12.5
02
277
60
1
2
3.0
10.9
208
3
3
2.25
6.3
240
3
3
3.0
7.3
480
3
4
3.0
3.7
208
1
2
4.5
21.7
240
1
2
6.0
25.0
03
277
60
1
2
6.0
21.7
208
3
3
4.5
12.6
240
3
3
6.0
14.5
480
3
4
6.0
7.3
208
1
2
5.7
27.5
240
1
2
7.5
31.3
04
277
60
1
2
7.5
27.1
208
3
3
5.7
15.9
240
3
3
7.5
18.1
480
3
4
7.5
9.1
208
1
2
7.9
38.0
240
1
2
10.5
43.8
06
277
60
1
2
10.5
38.0
208
3
3
7.9
21.9
240
3
3
10.5
25.3
480
3
4
10.5
12.7
Note: All data based on individual units. Electric heat will operate only with fan at high speed.
Installation
electrical
requirements
Содержание UniTrane FC
Страница 71: ...UNT SVX07A EN 71 typical wiring diagram Maintenance CSTI Fan Speed Switch...
Страница 72: ...72 UNT SVX07A EN typical wiring diagram Maintenance CSTI Non Fan Speed Switch...
Страница 73: ...UNT SVX07A EN 73 typical wiring diagram Maintenance Line voltage fan speed switch...
Страница 74: ...74 UNT SVX07A EN typical wiring diagram Maintenance Tracer ZN010 with electric heat...
Страница 75: ...UNT SVX07A EN 75 typical wiring diagram Maintenance Tracer ZN510 with main and auxilliary valves...
Страница 76: ...76 UNT SVX07A EN typical wiring diagram Maintenance ZN520 with 2 stage electric heat...
Страница 77: ......
Страница 78: ......
Страница 79: ......