System Settings 

Changing these settings will affect the operation of the heating/cooling system.

 

Î

To view and edit these settings:

Press the 

1. 

MENU

 button.

Press and hold the two middle buttons simultaneously until the 

2. 

Installer Settings

 menu is displayed.

Scroll to System Settings and press the 

3. 

Select

 button.

Scroll to the setting you want to change. Press the plus (

4. 

+

) or minus (

-

) button to adjust the setting.

Press the 

5. 

Done

 button when you are finished.

Note on Delta Settings: The Delta T Setting is the delta, or difference between, the setpoint and current temp for 

 

Î

determining when a heat or cool call comes on. The “delta” is the number of degrees 

away

 from the setpoint.

Setting

Range

Default Description

Schedule 
Enable

Y or N

N

When enabled, the local thermostats scheduler function is enabled.

Recovery 
Enable

Y or N

N

The Smart Recovery feature allows heating and cooling systems to gradually 
recover from an energy-saving set point temperature to a comfort set point tem-
perature. Smart Recovery calculates the time needed to adjust the temperature 
to the next program setting for the Morning and Evening schedules. When the 
thermostat is in Smart Recovery mode, the display will show “Recov”.

Smart Recovery is an option that allows the HVAC system to attempt to recover 
from a setback period and reach a desired comfort temperature set point by the 
beginning of your programmed comfort period.  This option allows the choice 
whether to use Smart Recovery.

· Recovery is from a nite setback to morning comfort (period 1), or day setback 
to evening comfort period (period 3).When in Recovery, the 4th status line will be 
labeled “Recov”
· Recovery works in heat or cool mode
· While in recovery, the Aux-Heat stage will never engage
· Maximum Smart Recovery time is one hour.

H/C Delta

3 - 15 degrees

3

Sets the minimum separation between heating and cooling setpoints. Attempts 
to lower the cooling below the heating setpoint by this amount will PUSH the 
heating setpoint down to maintain this separation. Same for setting the heating 
setpoint above the cooling setpoint, it will PUSH the cooling setpoint up to 
maintain this separation.

Heating Delta 
Stage 1 ON

1 to 8 degrees

1

Sets the delta from setpoint that stage 1 heating starts.

Heating Delta 
Stage 1 OFF

0 to 8 degrees

0

Sets the delta from setpoint that stage 1 heating stops. Stage 1 turns off at 
setpoint minus (-) Delta Stage 1.

Heating Delta 
Stage 2 ON

1 to 8 degrees

2

Sets the delta from setpoint that stage 2 heating starts.

Heating Delta 
Stage 2 OFF

0 to 8 degrees

0

Sets the delta from setpoint that stage 2 heating stops. Stage 2 turns off at 
setpoint minus (-) Delta Stage 2.

Heating Delta 
Aux Heat ON

1 to 8 degrees

3

Sets the delta from setpoint that Aux Heat starts. 

Heating Delta 
Aux Heat OFF

0 to 8 degrees

0

Sets the delta from setpoint that stage 1 heating stops. Aux Heat turns off at 
setpoint minus (-) Delta Aux Heat.

Cooling Delta 
Stage 1 ON

1 to 8 degrees 

1

Sets the delta from setpoint that stage 1 cooling starts. 

Cooling Delta 
Stage 1 OFF

0 to 8 degrees

0

Sets the delta from setpoint that stage 1 Cooling stops. Stage 1 turns off at 
setpoint plus (+) Delta Stage 1.

Cooling Delta 
Stage 2 ON

1 to 8 degrees 

2

Sets the delta from setpoint that stage 2 cooling starts.

Cooling Delta 
Stage 2 OFF

0 to 8 degrees

0

Sets the delta from setpoint that stage 2 Cooling stops. Stage 2 turns off at 
setpoint plus (+) Delta Stage 2.

30

Содержание TZEMT500AB32MAA

Страница 1: ...and air conditioning wholesalers that participate in the Thermostat Recycling Corporation s recycling program are available at www thermostat recyle org The TZEMT500 Thermostat is compatible with sing...

Страница 2: ...o ensure proper heating and cooling system operation Indoor Unit Type System Type Gas Furnace Single Stage Gas Furnace 1 Stage Cooling Multi Stage Gas Furnace 1 Stage Cooling 2 Stage Cooling Electric...

Страница 3: ...re G G W R C Connect wire G c Find the 24 VAC common terminal identified with the letter C X B or COM iThis terminal may already have a wire connected to it but it may not be a wire that is connected...

Страница 4: ...rane American Standard Weathertron or York COM C B R RC RH E X2 W W1 W2 Y AUX O G Y Y1 Y2 Other Brands COM C X R RC RH E X2 W W1 W2 Y AUX O B G F Y Y1 Y2 Lennox C X R RC VR V RH E X2 W W1 W2 Y AUX O R...

Страница 5: ...er of wall plate a Locate the new wall plate over existing opening b Mark two holes with pencil c Use a level to verify that the two hole locations are level d Correct hole locations as needed e 24C 2...

Страница 6: ...a Use 1 8 blade screwdriver to secure wires in terminals b 24C 24RC 24RH W1 W2 0 G Y1 Y2 RS1 RS1 RS2 RS2 CAUTION EQUIPMENT DAMAGE HAZARD Improper wiring can lead to equipment damage Follow the Termin...

Страница 7: ...Heating with 1 or 2 Stage Cooling Fan G Heat Stage 1 W1 Compressor Stage 1 Y1 24VAC Return R 24VAC Common B C Compressor Stage 2 Y2 BK Heat Stage 2 W2 RED GREEN WHITE YELLOW O R A N G E B R O W N BLUE...

Страница 8: ...Replaces internal sensor RS2 not connected Indoor sensor connected to RS2 Averages temperature with internal sensor RS1 not connected Indoor sensors connected to RS1 and RS2 Averages RS1 and RS2 senso...

Страница 9: ...ssor Stage 2 BK YLO Outdoor Unit Compressor Stage 1 Y1 24VAC Return R 24VAC Common B Compressor Stage 2 Y2 Note 4 Note 6 Note 2 Note 3 Note 4 R1 OIL BURNER PRIMARY Note 6 For 2 Step Cooling outdoor un...

Страница 10: ...ages temperatures with the internal sensor Use ZZSENSAL0400AA See Figure B If RS2 is set to indoor location IN Default selection in the thermostat installation set up menu and a sensor is attached to...

Страница 11: ...gh the installation steps and look for problems Pay special attention to steps 3 4 and 6 14 Route the wires per label on the mounting plate and attach the thermostat face to the wall plate Tuck wiring...

Страница 12: ...3or4to highlight the data you want to change Scroll up or down e or to make changes Press the f Set button when you are finished Press the g Done button twice to exit the menu Done Select Menu Selecti...

Страница 13: ...ress the f button to change the setting Electric If Single Stage System press Done 4 times and go to step 19 If Multistage System continue with steps g through j Scroll down to g 2nd Stage Heat Press...

Страница 14: ...temperature down using the scroll down button until the d new setpoint is below the room temperature Verify that the outdoor unit and the system fan come on and run e Perform System Checkout 20 FAN b...

Страница 15: ...t Scroll down to d Z Wave Install and press the Select button Press the e Yes button to enroll the thermostat Observe the lights on the bridge The orange light will blink f while enrollment is taking...

Страница 16: ...u have 30 seconds to complete the remainder of the steps Study the steps below before beginning Press and release the minus button on the bridge 3 Press the 4 MENU button on the thermostat Scroll down...

Страница 17: ...ast Adjustable on screen Buttons 6 LEDs 4 3 green 1 red Power 24VAC from HVAC System HVAC System Type Compatible Standard gas electric or Heat Pump Multistage System Compatible Standard HVAC Systems 2...

Страница 18: ...he Setpoint Up Down buttons change the heat setpoint In COOL mode they change the cooling setpoint In AUTO mode the buttons change the last call s heating or cooling setpoint The setpoints will push e...

Страница 19: ...Other thermostat menus can be accessed by pressing the MENU button System Mode Used to change the system mode Off System off Heating Heating only on Cooling Cooling only on Auto Heating Cooling on as...

Страница 20: ...lta Stg1 OFF Thermostat Info H Delta Stg2 ON H Delta Stg2 OFF H Delta AuxH ON H Delta AuxH OFF C Delta Stg1 ON C Delta Stg1 OFF C Delta Stg2 ON C Delta Stg2 OFF Max Heat SP Min Cool SP Min Run Time Mi...

Страница 21: ...Set Clock screen Set Clock Back Set Time 11 15 AM Date 01 01 09 Day Thu Set the Clock Press the 1 MENU button Scroll to 2 User Settings and press the Select button Scroll to 3 Set Clock and press the...

Страница 22: ...ilter Service and press the Select button The Filter Runtime is displayed in hours To reset the Filter Runtime counter press the 4 Reset button The Filter Runtime counter should be reset each time the...

Страница 23: ...Maintenance Service Done Reset Heat Runtime 200 HRS Cool Runtime 300 HRS Service Interval 3000 HRS Change the Maintenance Service Interval Press the 1 MENU button Scroll to 2 User Settings and press t...

Страница 24: ...t Press the 1 MENU button Scroll to 2 User Settings and press the Select button Scroll to 3 Screen Timeout Press the plus 4 or minus buttons to adjust the time in seconds The screen time out can be se...

Страница 25: ...ation of the internal temperature sensor The temperature calibration can be changed by 7 degrees When the Sensor Calibration screen is selected the current temperature calibration is displayed In the...

Страница 26: ...a lower number Backlite Display Backlite Timeout 60 Contrast 10 Done Adjust the Backlight Press the 1 MENU button Scroll to 2 User Settings and press the Select button Scroll to 3 Backlite Display and...

Страница 27: ...heating and cooling runtime hours for a week Energy Saving Mode ESM Setpoints are the setpoints used when the Energy Saving Mode schedule is selected in the Schedule Mode screen Energy Saving Mode Set...

Страница 28: ...00 9 ZNID 004 ZHID 01 07 37 bd System Type Standard Fan Type Gas Item Description TZEMT500AB32 Model Number Ver 01 00 10 Firmware version This number may vary ZVER 02 00 9 Z Wave version This number m...

Страница 29: ...sed but no menu options may be selected The Installer Settings hidden button operation is always operational allowing Display Lock to be turned off Max Heat SP 55F to 90F 12C 32C 90F 32C Sets the maxi...

Страница 30: ...ery the 4th status line will be labeled Recov Recovery works in heat or cool mode While in recovery the Aux Heat stage will never engage Maximum Smart Recovery time is one hour H C Delta 3 15 degrees...

Страница 31: ...ump system 2nd Stage Cool Y or N N Enables the 2nd Stage Cool operation Fan Cycler Settings Changing these settings will affect the operation of the heating cooling system To view and edit these setti...

Страница 32: ...edule Heat and Cool Preset Confort Preset Energy Star Done Select Enable Disable the Schedules Menu Because the Schedules menu is disabled by default you must first enable it before any scheduling can...

Страница 33: ...eset schedule with mild setbacks designed to maintain a comfortable temperature Preset Energy Star This is a preset schedule with deeper setbacks designed to conserve energy View the Current Schedule...

Страница 34: ...isplay Off Run Schedule mode is active On Hold Temperature hold is active On ESM Energy Savings Mode temperature preset is active LED 4 Red System Alert display Off None No alerts or messages On Filte...

Страница 35: ...ontrol if it is damaged while in your possession including but not limited to 1 damage caused by unreasonable use of the low voltage room comfort control 2 damage from failure to properly maintain the...

Страница 36: ...ions and design without notice Trane 6200 Troup Highway Tyler TX 75707 www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design an...

Отзывы: