31
SSP-PRC002-EN
Electrical
Data
Table ED-1— Electrical Characteristics — Motors — Air Handler
Standard Fan Motor
Oversized Fan Motor
Unit
Amps
Amps
Model No.
Volts
Phase
FLA
LRA
Phase
FLA
LRA
TWE050
380/415
3
1.4
8.2
3
1.8
21.6
TWE075
380/415
3
3.2
19.7
3
4.0
25.5
TWE100
380/415
3
3.6
25.5
3
5.3
37.5
TWE155
380/415
3
4.6
37.5
3
6.9
39.2
TWE200
380/415
3
7.6
39.2
3
9.0
65.1
Table ED-2 — Unit Wiring — Air Handler
Minimum
Maximum Fuse
Unit
Unit Operating
Circuit
Size or Maximum
Model No.
Voltage Range
Ampacity
Circuit Breaker
TWE050
380/415
2
15
TWE075
380/415
4
15
TWE100
380/415
5
15
TWE155
380/415
6
15
TWE200
380/415
10
15
Table ED-4 — Unit Wiring — Heat Pumps
Minimum
Maximum Fuse
Unit
Unit Operating
Circuit
Size or Maximum
Model No.
Voltage Range
Ampacity
Circuit Breaker
TWA075
380/415
12.6
50
TWA100 380/415
2
2 .5
35
TWA155 380/415
28.4 35
TWA200 380/415
41.0
50
Table ED-3— Electrical Characteristics — Motors — 50 Cycle — Heat Pumps
Compressor Motor
Condenser Fan Motor
Amps
Amps
Unit
RLA
LRA
FLA
LRA
Model No.
No.
Volts
Phase
(Ea.)
(Ea.)
No.
Volts
Phase
(Ea.)
(Ea.)
TWA075AD 1 380/415 3 8.8 90.0 1 380/415 1 1.6 3.7
TWA100AD 1 380/415 3 1
5.8
1
24
.0 1 380/415 1 2.7 7.0
TWA155BD
2
380/415
3
11.2
94.8
2
380/415
1
1.6
3.7
TWA200BD 2 380/415 3
15.8
1 2 4 .
0 2 380/415 1 2.7 7.0
Содержание TWE050A
Страница 35: ...35 SSP PRC002 EN Typical Wiring Heat Pump...
Страница 37: ...37 SSP PRC002 EN Typical Wiring Heat Pump...
Страница 54: ......
Страница 55: ......