Clearances

Provide enough space around the unit 
to allow unrestricted access to all 
service points. Refer to Figure 1 for 
unit dimensions and minimum 
required service and free air 
clearances. Observe the following 
points to insure proper unit operation.

1.

Do not install the unit under a low 
overhang. Condenser discharge 
must not be restricted. See Note 
in Figure 1.

Note:

Important!

 

Do not obstruct 

condenser discharge air. 
This can result in warm air 
recirculation through the 
coil.

2.

Do not locate the unit in a 
position where runoff water can 
fall into the fan discharge 
openings.

3.

Condenser intake air is supplied 
from three sides of the unit. 
Adhere to the minimum required 
clearances given in Figure 1.

Unit Mounting

Rooftop Mounting

If the unit will be roof mounted, 
determine for certain that the 
structure is strong enough to support 
the unit and any required accessories. 
Unit weights are given in Table 2. The 
unit should be elevated on a level, 
field fabricated four-inch steel or 
wood 4" x 4" mounting frame. 
Complete the frame and secure it into 
position before lifting the unit to the 
roof. The mounting frame must 
support a minimum of three of the 
unit’s four sides and should span roof 
supports to distribute the load on the 
roof.

Figure 2.

Roof Mounted Unit

WARNING

Mounting Integrity!

Ensure that the roof structure 
supports are strong enough to 
support the weight of the unit and 
any accessories. Failure to do so could 
result in death or serious injury or 
possible equipment or property-only 
damage.

The following warning complies with 
State of California law, Proposition 65.

WARNING

Fiberglass Wool!

Product contains fiberglass wool. 
Disturbing the insulation in this 
product during installation, 
maintenance or repair will expose you 
to airborne particles of glass wool 
fibers and ceramic fibers known to 
the state of California to cause cancer 
through inhalation. Glass wool fibers 
may also cause respiratory, skin or 
eye irritation.

Ground Level Mounting

For ground level installation, the unit 
base should be adequately supported 
and hold the unit near level. The 
installation must meet the guidelines 
set forth in local codes. The support 
should extend two inches beyond the 
unit base channels at all points. The 
unit and support must be isolated 
from any adjacent structure to prevent 

possible noise or vibration problems. 
Any ground level location must 
comply with required clearances 
given in Figure 1.

Refrigerant Piping

Structural Preparation

Holes must be made in the structure 
to run refrigerant lines. For the 
majority of ground-level installations, 
the holes can be made in the header 
that rests on top of the foundation. 
Alternatively, these holes may also be 
made in the foundation itself. On roof-
mounted units, refrigerant lines 
should enter the building as close to 
the unit as possible; preferably within 
three to four inches of the refrigerant 
connection on the unit, plus a six-inch 
(long radius) 90 degree ell entering 
the building, Figure 2.

Refrigerant Piping Guidelines

1.

Maximum recommended line 
lengths (per circuit):  

2.

Maximum allowable pressure 
drops (R410A):

Note:

Route refrigerant piping for 
minimum linear length, mini-
mum number of bends and 
fittings (no reducers) and 
minimum amount of line 
exposed to outdoor ambients.

3.

Recommended line sizes TTA200 
and 240F (two speed):

Note:

Insulate all refrigerant piping 
and connections.

Maximum linear length.......... 150 Ft.

(w/o accumulator)

Maximum suction line lift......

50 Ft.

Maximum liquid line lift ........

50 Ft.

Suction Line............................

5 psi

Liquid Line............................... 50 psi

Suction Line

1 5/8" sealed type L 
refrigerant tubing

Liquid Line

5/8" sealed type L 
refrigerant tubing

Installation

!

!

Содержание TTA200FD Series

Страница 1: ...TTA SVN03A EN June 2006 Installation Operation Maintenance Split System Cooling Condensers 20 Ton Model 60 Hz TTA240F A Model 50 Hz TTA200FD A...

Страница 2: ...n must conform with National Electric Code ANSI NFPA NO 70 LATEST REVISION Note Do Not release refrigerant to the atmosphere If adding or removing refrigerant is required the service technician must c...

Страница 3: ...ce and Cautions and Warnings 2 Model Number Description 4 Electrical Data 6 Installation 7 System Prestart Procedure 15 System Test Mode ReliaTel 18 Troubleshooting ReliaTel 19 Maintenance 22 Warranty...

Страница 4: ...CT TYPE TTA Split System Cooling DIGITS 4 6 NOMINAL GROSS COOLING CAPACITY MBh 200 200 MBh 240 240 MBh DIGIT 7 REFRIGERATION CIRCUIT A 1 Refrigerant Circuit R22 B 2 Refrigerant Circuit R22 C Manifold...

Страница 5: ...imensional Data Connection Location Clearances Corner Weights APPROXIMATE CORNER WEIGHT MASS TOTAL UNIT WEIGHT TOTAL SHIPPING WEIGHT MODEL NO 1 2 3 4 TTA240F A 292 lbs 181 lbs 222 lbs 140 lbs 835 lbs...

Страница 6: ...Circuit Fuse Amps Amps Number Characteristics Range Ampacity Size Qty RLA LRA Qty HP FLA LRA TTA240F3 208 230 60 3 187 254 89 4 110 2 35 3 239 0 2 1 5 0 14 4 TTA240F4 460 60 3 414 506 46 6 60 2 18 5 1...

Страница 7: ...it is stored and as soon as possible after delivery Concealed damage must be reported within 15 days If concealed damage is discovered stop unpacking the shipment Do not remove damaged material from t...

Страница 8: ...allation maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation Glass wool fibers may a...

Страница 9: ...fold valve for the line that is connected to the suction line service valve Disconnect the line from the gauge port on the valve Figure 4 Refrigerant Piping Procedure Indoor Unit Once liquid and sucti...

Страница 10: ...removed and power is applied to the unit Failure to observe all safety precautions could result in severe personal injury or death 2 Turn on power to the unit Allow the system to run for five to ten...

Страница 11: ...storing components provided by Trane or others refer to the appropriate manufacturer s literature for allowable waiting periods for discharge of capacitors Verify with an appropriate voltmeter that al...

Страница 12: ...or 10 wires maximum 24 volts of wires are dependent upon zone sensor selection F NSB Panel 8 wires 24 volts Figure 6 Typical Field Wiring ReliaTel Control Note 1 Wiring shown with dashed lines is to b...

Страница 13: ...TTA SVN03A EN 13 Installation Figure 7 Night Setback Panel Field Wiring Figure 8 Zone Sensor Field Wiring Figure 9 Thermostat Field Wiring...

Страница 14: ...14 TTA SVN03A EN Installation Figure 10 TTA240F TWE240E Refrigerant Circuit...

Страница 15: ...s returned to normal the compressor will cycle back on Internal Overload Protector IOL This device is a thermal actuated snap disc imbedded in the compressor It will shut off the compressor if the dis...

Страница 16: ...ON AUTO switch on the room thermostat With the switch positioned at AUTO and the system operating in the cooling mode fan operation coincides with the cooling run cycles If the system is equipped with...

Страница 17: ...ditional cooling For Thermostat Control When the room thermostat system switch is positioned at COOL and the fan switch is at AUTO the RTRM energizes the compressor relay coil located on the RTRM duri...

Страница 18: ...Mode will be ignored if a short is present across Test 1 and Test 2 at start up 2 Resistance Test Mode This method can be used for start up providing a decade box for variable resistance outputs is a...

Страница 19: ...n to start the unit This procedure will allow you to check all of the RTRM outputs and all of the external controls relays contactors etc that the RTRM outputs energize for each respective mode Procee...

Страница 20: ...use LED s for quick status information at the unit purchase a BAYSENS010B ZSM and connect wires with alligator clamps to terminals 6 through 10 Connected each respective terminal wire 6 through 10 fr...

Страница 21: ...forward direction If high resistance in both directions LED is open If low in both directions LED is shorted Method 3 To test LED s with ZSM connected to unit test voltages at LED terminals on ZSM A m...

Страница 22: ...ation 1 Perform all of the monthly maintenance inspections 2 With the unit operating check unit superheat and record the reading in the Maintenance Log 3 Remove any accumulation of dust and or dirt fr...

Страница 23: ...Log Date Ambient Temp F Evaporator Entering Air Compressor Superheat Circuit 1 F Subcooling Circuit 1 F Dry Bulb Wet Bulb Suction Pressure Discharge Pressure Perform each inspection once per month du...

Страница 24: ...hall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective THE WARRANTY AND LIABI...

Страница 25: ...conforming to this warranty Warrantor shall not be obligated to pay for the cost of lost refrigerant No liability whatever shall attach to Warrantor until said products have been paid for and then sa...

Страница 26: ...26 TTA SVN03A EN...

Страница 27: ...TTA SVN03A EN 27...

Страница 28: ...nuous product and data improvement and reserves the right to change design and specifications without notice Literature Order Number TTA SVN03A EN File Number SV UN TTA SVN03A EN 06 06 Supersedes New...

Отзывы: