Trane TTA200FD Series Скачать руководство пользователя страница 15

TTA-SVN03A-EN

15

Safety Controls

Note:

All of these controls may not 
be installed on your unit, 
check electrical schematic.

Low Outdoor Ambient Cooling

The Evaporator Defrost Control is 
standard equipment on Air Handlers 
and will permit low ambient cooling 
down to 50 degrees F. For cooling 
operation down to 0 degrees F, use an 
Accessory Head Pressure Control on 
the outdoor unit.

Evaporator Defrost Control (EDC)

This control is located in the Air 
Handler of Split Units. The control’s 
sensing tube is imbedded vertically in 
the evaporator coil, near the center. 
This device will stop the compressor if 
the indoor coil temperature drops 
below its setting. The indoor air will 
still circulate across the coil bringing 
the temperature of the coil back up to 
the cut-in temperature of the 
evaporator defrost control.

Low Pressure Cut-Out (LPCO)

This control’s sensor is located in the 
suction (gas) line, near the 
compressor. This control will stop the 
compressor and the outdoor fans if 
suction pressure drops below the Low 
Pressure Cut-Out setting. Once the 
suction pressure has returned to 
normal, the compressor and outdoor 
fans will cycle back on.

High Pressure Cut-Out (HPCO)

This control’s sensor is located in the 
discharge line. This device will shut 
off the compressor and the outdoor 
fan(s) if the discharge pressure 
exceeds the High Pressure Cut-Out’s 
setting. Once the discharge pressure 
has returned to normal, the 
compressor will cycle back on.

Internal Overload Protector (IOL)

This device is a thermal actuated snap 
disc, imbedded in the compressor. It 
will shut off the compressor if the 
discharge temperature of the 
compressor exceeds its design trip 
temperature.

Note:

The IOL will put the 
compressor back in operation 
once the compressor motor 
heat has dropped below the 
trip setting; however, a check 
of the refrigerant and 
electrical systems should be 
made to determine the cause 
and be corrected.

Installation Checklist

Complete this checklist once the unit 
is installed to verify that all 
recommended procedures have been 
accomplished before starting the 
system. Do not operate the system 
until all items covered by this checklist 
are complete.

[ ]  Inspect unit location for proper 
required service clear-ances.

[ ]  Inspect unit location for proper free 
air clearances.

[ ]  Inspect unit location for secure, 
level mounting position.

[ ] Performed initial leak test?

[ ] Connected properly sized and 
constructed liquid and suction lines to 
the connection stubs at both the 
indoor and outdoor units?

[ ] Insulated the entire suction line?

[ ] Insulated portions of liquid line 
exposed to extremes in temperature?

[ ] Evacuated each refrigerant circuit 
to 350 microns?

[ ] Charged each circuit with proper 
amount of R410A?

Electrical Wiring

[ ] Provided unit power wiring (with 
disconnect) to proper terminals in the 
unit control section?

[ ]  Installed system indoor 
thermostat?

[ ]  Installed system low voltage 
interconnecting wiring to proper 
terminals of outdoor unit, indoor unit 
and system thermostat?

System Pre-Start Procedure

Содержание TTA200FD Series

Страница 1: ...TTA SVN03A EN June 2006 Installation Operation Maintenance Split System Cooling Condensers 20 Ton Model 60 Hz TTA240F A Model 50 Hz TTA200FD A...

Страница 2: ...n must conform with National Electric Code ANSI NFPA NO 70 LATEST REVISION Note Do Not release refrigerant to the atmosphere If adding or removing refrigerant is required the service technician must c...

Страница 3: ...ce and Cautions and Warnings 2 Model Number Description 4 Electrical Data 6 Installation 7 System Prestart Procedure 15 System Test Mode ReliaTel 18 Troubleshooting ReliaTel 19 Maintenance 22 Warranty...

Страница 4: ...CT TYPE TTA Split System Cooling DIGITS 4 6 NOMINAL GROSS COOLING CAPACITY MBh 200 200 MBh 240 240 MBh DIGIT 7 REFRIGERATION CIRCUIT A 1 Refrigerant Circuit R22 B 2 Refrigerant Circuit R22 C Manifold...

Страница 5: ...imensional Data Connection Location Clearances Corner Weights APPROXIMATE CORNER WEIGHT MASS TOTAL UNIT WEIGHT TOTAL SHIPPING WEIGHT MODEL NO 1 2 3 4 TTA240F A 292 lbs 181 lbs 222 lbs 140 lbs 835 lbs...

Страница 6: ...Circuit Fuse Amps Amps Number Characteristics Range Ampacity Size Qty RLA LRA Qty HP FLA LRA TTA240F3 208 230 60 3 187 254 89 4 110 2 35 3 239 0 2 1 5 0 14 4 TTA240F4 460 60 3 414 506 46 6 60 2 18 5 1...

Страница 7: ...it is stored and as soon as possible after delivery Concealed damage must be reported within 15 days If concealed damage is discovered stop unpacking the shipment Do not remove damaged material from t...

Страница 8: ...allation maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation Glass wool fibers may a...

Страница 9: ...fold valve for the line that is connected to the suction line service valve Disconnect the line from the gauge port on the valve Figure 4 Refrigerant Piping Procedure Indoor Unit Once liquid and sucti...

Страница 10: ...removed and power is applied to the unit Failure to observe all safety precautions could result in severe personal injury or death 2 Turn on power to the unit Allow the system to run for five to ten...

Страница 11: ...storing components provided by Trane or others refer to the appropriate manufacturer s literature for allowable waiting periods for discharge of capacitors Verify with an appropriate voltmeter that al...

Страница 12: ...or 10 wires maximum 24 volts of wires are dependent upon zone sensor selection F NSB Panel 8 wires 24 volts Figure 6 Typical Field Wiring ReliaTel Control Note 1 Wiring shown with dashed lines is to b...

Страница 13: ...TTA SVN03A EN 13 Installation Figure 7 Night Setback Panel Field Wiring Figure 8 Zone Sensor Field Wiring Figure 9 Thermostat Field Wiring...

Страница 14: ...14 TTA SVN03A EN Installation Figure 10 TTA240F TWE240E Refrigerant Circuit...

Страница 15: ...s returned to normal the compressor will cycle back on Internal Overload Protector IOL This device is a thermal actuated snap disc imbedded in the compressor It will shut off the compressor if the dis...

Страница 16: ...ON AUTO switch on the room thermostat With the switch positioned at AUTO and the system operating in the cooling mode fan operation coincides with the cooling run cycles If the system is equipped with...

Страница 17: ...ditional cooling For Thermostat Control When the room thermostat system switch is positioned at COOL and the fan switch is at AUTO the RTRM energizes the compressor relay coil located on the RTRM duri...

Страница 18: ...Mode will be ignored if a short is present across Test 1 and Test 2 at start up 2 Resistance Test Mode This method can be used for start up providing a decade box for variable resistance outputs is a...

Страница 19: ...n to start the unit This procedure will allow you to check all of the RTRM outputs and all of the external controls relays contactors etc that the RTRM outputs energize for each respective mode Procee...

Страница 20: ...use LED s for quick status information at the unit purchase a BAYSENS010B ZSM and connect wires with alligator clamps to terminals 6 through 10 Connected each respective terminal wire 6 through 10 fr...

Страница 21: ...forward direction If high resistance in both directions LED is open If low in both directions LED is shorted Method 3 To test LED s with ZSM connected to unit test voltages at LED terminals on ZSM A m...

Страница 22: ...ation 1 Perform all of the monthly maintenance inspections 2 With the unit operating check unit superheat and record the reading in the Maintenance Log 3 Remove any accumulation of dust and or dirt fr...

Страница 23: ...Log Date Ambient Temp F Evaporator Entering Air Compressor Superheat Circuit 1 F Subcooling Circuit 1 F Dry Bulb Wet Bulb Suction Pressure Discharge Pressure Perform each inspection once per month du...

Страница 24: ...hall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective THE WARRANTY AND LIABI...

Страница 25: ...conforming to this warranty Warrantor shall not be obligated to pay for the cost of lost refrigerant No liability whatever shall attach to Warrantor until said products have been paid for and then sa...

Страница 26: ...26 TTA SVN03A EN...

Страница 27: ...TTA SVN03A EN 27...

Страница 28: ...nuous product and data improvement and reserves the right to change design and specifications without notice Literature Order Number TTA SVN03A EN File Number SV UN TTA SVN03A EN 06 06 Supersedes New...

Отзывы: