Input/output functions and wiring for typical applications
Figure 11. Four-pipe heating/cooling unit with auto changeover
LonTalk
in
Outdoor air or
generic temperature
24 V
†
Exhaust (or fan, medium speed)
24 V
†
Fan, low speed
24 V
†
Fan, high speed
Low-coil-temperature detection
(closed=normal)*
Condensate overflow (closed=normal)*
Occupancy (open=occupied)*
LonTalk
H
N
24 Vac
24 V
†
Generic/baseboard heat
24 V
†
Heating/cooling changeover valve
out
Fan status (closed=on)*
24 V
†
Outdoor air damper actuator
Discharge air
temperature
24 V
†
Auxiliary heating valve
Open
Clos
e
Open
Clos
e
Entering water
temperature
Op
en
Cl
os
e
* All binary inputs are configurable.
†
Connect 24 V to an AC POWER (24V) terminal.
AI4 input: See
Figures
and
on
for wiring
options