Input/output functions and wiring for typical applications
Figure 6.
AI4 terminal wiring: RH measurement
Binary outputs
The ZN521 zone controller supports fan coil, blower coil, and unit ventilator applications that may
include the following components:
•
Supply fan with up to three speeds
•
Hydronic cooling and/or heating coils with two-position or tri-state modulating control valve
•
DX cooling (single stage)
•
Electric heat (single stage or two stage)
•
Baseboard heat (single stage)
•
Tri-state modulating outdoor/return air damper
•
Tri-state modulating face-and-bypass damper
The Tracer ZN521 controller includes ten binary outputs. Each binary output is a triac with a rating
of 12 VA at 24 Vac.
describes the function of each output.
Tracer ZN521
RH sensor
Table 6.
Binary output functions
Binary output
Functions
1
• Fan high
2
• Fan medium
• Exhaust fan or damper
3
• Fan low
4
• Modulating cooling/changeover valve, open
• Two-position cooling/changeover valve
• DX cooling
5
• Modulating cooling/changeover valve, close
• Face-and-bypass damper, open to face
6
• Modulating heating valve, open
• Two-position heating valve
• Electric heat, stage 1
7
• Modulating heating valve, close
• Face-and-bypass damper, close (bypass)
• Electric heat, stage 2
8
• Outdoor air damper, open (return air damper, close)
9
• Outdoor air damper, close (return air damper, open)
10
• Baseboard heat
• Generic