CNT-SVX04A-EN
76
Configuration
With the Rover service tool, you can calibrate two of the controller’s analog
inputs: space temperature and setpoint. For each input, the calibration value is
added to the measured value to determine the effective value.
■
Space temperature (±10.0ºF, 0.1ºF resolution)
■
Local setpoint (±10.0ºF, 0.1ºF resolution)
Configurable parameters
Unit type
■
Fan coil
■
Blower coil
■
Unit ventilator
Rover service tool uses the unit type (fan coil, blower coil, or unit ventilator) to
determine and download many other aspects of the unit configuration, such as
the default analog input configuration, the default binary input configuration,
and the default binary output configuration. See Tables 43 through 54 on page
79 and Table 69 on page 102.
Cooling source
■
None
■
Hydronic (main coil changeover)
■
Dedicated hydronic
■
DX
Heating source
■
None
■
Hydronic
■
Dedicated hydronic
■
Steam
■
Electric heat
■
Hydronic (main coil changeover) + dedicated hydronic (auxiliary coil)
■
Hydronic (main coil changeover)