2

CNT-PRC003-EN

Tracer VV550 and Tracer VV551 variable 
air volume (VAV) controllers provide 
single-duct digital control for VAV boxes. 
They support the following VAV control 
sequences:

• Space temperature control
• Flow tracking
• Ventilation flow control

The Tracer VV550 VAV controller is 
available factory-installed on Trane 
VariTrane VAV boxes (Figure 1). The 
Tracer VV551 VAV controller is available 
for field installation for a variety of VAV 
applications (Figure 2).

Figure 1. Tracer VV550 controller 

Figure 2. Tracer VV551 controller 
(uses same board as Tracer VV550)

Because the Tracer VV550 and Tracer 
VV551 VAV controllers use the same 
logic controller, both offer the same 
wide range of application and control 
flexibility. The Tracer VV551 VAV 
controller includes additional labor-
saving packaging features for field-
installed applications.

Tracer VV550/551 VAV controllers can 
operate as part of a Trane Integrated 
Comfort™ system (ICS), as part of a 
building management system from 
another manufacturer, or as a 
standalone device.

When it is part of a Trane ICS, a Tracer 
VV550/551 VAV controller enables the 
building automation system (BAS) to 
perform functions such as scheduling, 
trending, alarming, remote 
communications, and VAV air system 
(VAS) coordination. The controller 
communicates with a Tracer Summit 
BAS over the LonTalk

®

 communications 

link. The controller can also 
communicate with other building control 
systems that are compliant with the 
LonMark

®

 Space Comfort Controller 

(SCC) profile.

Tracer VV550/551 VAV controllers can be 
configured using the Rover

 service 

tool. They have the following inputs and 
outputs (Figure 3 on page 6): 

Analog inputs:

• Space temperature (10 k

thermistor)

• Space setpoint (1 k

potentiometer)

• Primary/discharge air temperature 

(10 k

 thermistor)

• Primary air flow

Binary inputs:

• Occupancy or generic

Binary outputs:

• Air valve close
• Air valve open
• Heat  1
• Heat  2
• Heat 3 or fan On/Off

Introduction

© 2005 American Standard

All rights reserved

™ ® The following are trademarks or registered trademarks of their respective compa-
nies: ICS, Rover, Tracer, Tracer Summit, and Trane of American Standard Inc.; LonMark, 
LonTalk, and LonWorks of the Echelon Corporation.

Содержание Tracer VV550

Страница 1: ...CNT PRC003 EN October 2005 Tracer Controls Tracer VV550 551 VAV Controllers...

Страница 2: ...other manufacturer or as a standalone device When it is part of a Trane ICS a Tracer VV550 551 VAV controller enables the building automation system BAS to perform functions such as scheduling trendin...

Страница 3: ...Auto commissioning sequence 5 Manual test function 5 Drive minimum and maximum from zone sensor 5 Trane controller compatibility 5 Interoperability 5 Wiring diagram 5 Wiring diagram for Tracer VV550...

Страница 4: ...to a floor area With this feature the installer can quickly configure the flow control boxes and set up the system without the need for custom programming Local versus remote reheat flexibility Tracer...

Страница 5: ...hat includes a thumbwheel setpoint a Tracer VAV VV550 551 controller can easily be overridden to minimum and maximum flow By simply turning the thumbwheel to the controller drives the air valve to the...

Страница 6: ...3 Tracer VV550 551 wiring diagram 3 2 1 On Cancel Binary input Trane zone sensor In Out Rover service tool Analog inputs Binary outputs LonTalk communication link 24V GND Wiring diagram for Tracer VV...

Страница 7: ...nication link Figure 4 Cancel ON 85 80 75 70 65 60 55 50 o o o TM ROVER Cancel ON 85 80 75 70 65 60 55 50 Cancel ON 85 80 75 70 65 60 55 50 Figure 4 Network architecture with Tracer VV551 VAV controll...

Страница 8: ...e 5 Contact your Trane sales office about other compatible zone sensors Figure 5 Zone sensors for use with Tracer VV550 551 GCC order number Zone Timed override buttons LCD Comm jack Setpoint thumbwhe...

Страница 9: ...stor 10 k 77 F 25 C From 14 to 122 F 10 to 50 C Space setpoint potentiometer 1 k From 50 to 90 F 10 to 32 2 C Primary discharge air temperature thermistor 10 k 77 F 25 C From 40 to 212 F 40 to 100 C P...

Страница 10: ...10 CNT PRC003 EN Figure 6 Tracer VV551 dimensions 7 5 in 19 2 cm 6 5 in 16 7 cm 6 5 in 16 7 cm 7 5 in 19 2 cm 5 5 in 14 0 cm Cover off Cover on...

Страница 11: ...nvoStatus SNVT_obj_status Space CO2 nviSpaceCO2 SNVT_ppm Alarm message nvoAlarmMessage SNVT_str_asc Clear alarms diagnostics nviRequest SNVT_obj_request Part of the node object Air flow setpoint input...

Страница 12: ...and specifications without notice Literature Order Number CNT PRC003 EN File Number PL ES CNT PRC003 1005 Supersedes CNT PRC003 EN April 2004 Stocking Location Inland Trane A business of American Stan...

Отзывы: