10
BAS-SVX065E-EN
Additional Components
The UC400 Controller requires the use of additional components for monitoring and proper
control of associated equipment. The use of specific components is dependent on the type of
application.
N
No
otte
e:: Additional components are not included with the UC400 Controller.
Water, Discharge, and Outdoor Air Temperature Sensors
Temperature sensors must be Trane 10 kΩ (at 25°C) thermistors. Entering water and discharge air
inputs can use a sealed temperature sensor (part numbers 4190 1100 and 4190 1133).
Binary Input Switching Devices
Occupancy, condensate overflow, compressor protection, frost detection, and fan status inputs
accept switching devices that may have normally open (NO) or normally closed (NC) dry
contacts.
Zone Temperature Sensors
The following table provides the sensor types and features supported by the UC400 Controller.
Table 3. UC400 controller supported sensors and features
Features
Sensor
Type
Setpoint
Fan
Control
System
Occupancy
LEDs
Part
Number
BAYSENS
Global
Parts
Temperature
Sensor
No
No
No
No
No
X1351152801
BAYSENS077A
SEN01448
No
Yes
X1351153001
BAYSENS073A
SEN01450
Temperature
Sensors w/
Fan Control
Single
•
Off
•
Auto
No
Yes
No
X1379084501
N/A
SEN01521
Single
•
Off
•
Auto
•
Low
•
High
Yes
X1379084801
SEN01524
Single
•
Off
•
Auto
•
Low
•
Medium
•
High
Yes
X1379084201
SEN01518
Temperature
Sensor w/
LCD Display
(a)
Single
•
Off
•
Auto
•
Low
•
Medium
•
High
No
Can be
configured
for
occupancy
No
X1379088604
N/A
N/A