background image

4

6

©2020 Trane

Trane has a policy of continuous product and product data improvement and reserves 
the right to change design and specifications without notice. We are committed to using 
environmentally conscious print practices.

Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates 
comfortable, energy efficient indoor environments for commercial and residential 
applications. For more information, please visit trane.com or tranetechnologies.com.

Wiring and Applying Power

1. Connect one end of the provided IMC power cable to the IMC connection on the Tracer SC.

Connect the other end of the IMC power cable to the IMC connection on the power supply module. 

2. Wire the 24 Vac input connection to a dedicated 24 Vac, Class 2 transformer.
3. Ensure the PM014 is properly grounded.

Important:

This device must be grounded for proper operation!

 The factory-supplied ground 

wire must be connected from any chassis ground connection on the device (

) to 

an appropriate earth ground (

). The chassis ground connection can be the 24 Vac 

transformer input at the device, or any other chassis ground connection on the 
device.

Note: 

Neither the Tracer SC nor the PM014 is grounded through the DIN rail connection.

4. Apply power to the Tracer SC by pressing the power button.

All status LEDs illuminate and the following sequence flashes on the 7-segment display:

8, 7, 6, 5, 4, L, dancing dash pattern

. The dancing dashes continue while the Tracer SC

is operating normally. 

Note: 

For more information see “Tracer SC Installation and Setup Guide,” BAS-SVX31, 

and “Power Supply Module PM014 Installation, Operation, and Maintenance”, BAS-SVX33.

PM014

24

VAC

XFMR

OUT

24

VAC

24

VAC

XFMR

OUT

24

VAC

Tracer SC

IMC 

connections

Note: A pigtail connection 

should be used between the 

chassis ground on the 

device and an earth ground, 

if the device is not grounded 

through one leg of the 

transformer wiring.

24 Vac output

24 Vac input

IMC cable

PM014

24 Vac Transformer

Specifications

Agency Listings and Compliance

The European Union (EU) Declaration of Conformity is available from 
your local Trane

®

 office.

Table 1.

Tracer SC Specifications

Power Requirements

(From PM014) 24 Vdc @ 0.3A; 14VA max (PM014 input VA).

Storage

Temperature:

-40°C to 70°C (-40°F to 158°F)

Relative humidity:

Between 5% to 95% (non-condensing)

Operating Environment

Temperature:

-40°C to 50°C (-40°F to 122°F)

Humidity:

Between 10% to 90% (non-condensing)

Input power:

24 Vac

Product weight

1 kg (2.2 lb.)

Altitude:

Maximum 2,000 m (6,500 ft.)

Installation:

Category 3

Pollution

Degree 2

BAS-SVN215J-EN 11 Dec 2020

Supersedes X39641154-01H (Mar 2016) 

Tracer SC front panel

power 

button

7-segment 

display

Отзывы: