Installation and Maintenance
67
Motor runs and then dies down
Partial loss of line voltage
Check for loose connections.
Determine adequacy of main power
supply.
Stator shorts when motor warms up
Replace stator.
Motor does not come up to
speed
Low voltage at motor terminals
Check voltage across AC line and
correct voltage loss if possible.
Line wiring to motor too small
Replace with larger sized wiring.
Motor overheats
Overloaded motor
Reduce load or replace with a larger
motor.
Motor fan is clogged with dirt
preventing proper ventilation
Remove fan cover, clean fan and
replace cover.
Excessive motor noise
Motor mounting bolts loose
Tighten motor mounting bolts.
Rigid coupling connections
Replace with flexible connections.
Worn motor bearings
Replace bearings and seals.
Fan rubbing on fan cover
Remove interference in motor fan
housing.
Rapid motor bearing wear
Excessive overhung load due to
overtensioned drive
Check belt tension and overhung load.
Excessive overhung load due to a
small diameter motor sheave
Replace sheave with larger one.
Loose fan belt
Motor is poorly positioned
Adjust belt tension.
Worn or damaged belt
Replace belt or belt set. Check sheave
alignment.
Worn sheaves
Replace sheaves.
Shorter belt life
Worn sheaves
Replace sheaves.
Misaligned belt
Realign drive with MVP sheave set at
mean pitch diameter.
Grease or oil on belts
Check for leaky bearings. Clean belts
and sheaves.
Belt slipping
Adjust tension.
Belts rubbing
Remove obstruction or realign drive
for clearance.
Bearing noise
Poor alignment
Loosen bearing set screws and realign
(See Figure 50 .)
Inadequate lubrication
Grease bearing(s).
Low coil capacity
(Chilled water)
Air is bypassing coil
Prevent bypass with block-offs.
Coil tubes are blocked
Clean and unblock tubes.
Incorrect airflow
Check fan operating conditions.
Incorrect gpm
Check water pumps, valves and lines
for obstructions.
Incorrect water temperature
Provide proper water temperature.
Low coil capacity (Refrigerant)
Air is bypassing coil
Prevent bypass with block-offs.
Coil tubes are blocked
Clean and unblock tubes.
Incorrect airflow
Check fan operating conditions.
Expansion valve not operating
Check sensing bulb location and TXV
operation.
Table 52
T-Series Climate Changer Trouble Analysis
SYMPTOM
PROBABLE CAUSE
RECOMMENDED ACTION