Installation
8
PART-SVN237B-EN
Example: C H H S R B 1 A 1 X X
Phase motion motors (Early GP4 classic) (Common Mode Choke
(cores) will need to be ordered)
A1
(future use)
B1
145-010
Motor designations from Phase part
numbers -
C1
170-011
First 3 digits correspond to motor
length (A - F in Trane model number)
C2
170-095
Last 3 digits correspond to winding
characteristics. (Numeric digit in Trane
model number)
D1
(future use)
E1
165-010
E2
165-014
E3
165-016
F1
190-011
F2
190-014
GP4 Classic Regal Motors (Regal part number shown) (Common
Mode Choke (cores) will not need to be ordered):
BA
2520869-003
100T
SL
460V
BB
2520869-004
100T
SL
380V
CA
2520869-001
100T
HL
460V
CB
2520869-002
100T
HL
380V
EA
2520867-005
125T
SL
460V
EB
2520867-006
125T/150T SL
380V/460V
EC
2520867-007
150T
SL
380V
FA
2520867-001
150T
HL
460V
FB
2520867-002
150T
HL
380V
FC
2520867-003
165T
HL
460V
FD
2520867-004
165T
HL
380V
Table 6.
Common mode chokes
Description
Quantity
Mnemonic
PN
Common Mode
Core Assembly
One (1) per
circuit
COR00252
50711456
Individual
Conductor Core
Five (5) per
conductor
COR00253
X13641390010
Note: These parts must be sourced locally.
6. Inline connectors
With removal of the output inductor, the power
conductors will be need to be spliced together. Polaris
Electrical Connectors are recommended (Catalog No.: IT-
250). Six (6) pieces are needed. There are two conductors
per phase.
Figure 2.
Insulated in-line connectors
7. Piping and fitting changes may be required. Source
locally.
8. Insulation
All units require field installed insulation. Install insulation
before adding refrigerant for proper adhesion.
Heater Information
There are two heaters per compressor:
1. One cartridge/rod style that is the same part number
for both R and S frame compressors. This part number
changed between GP4 classic and VVi. Heaters need to
be ordered as separate service parts for the retrofit to
work. See
for the correct part numbers to
order.
2. The band style has not change between GP4 Classic
and VVi. The existing band style heaters on the RTAE
compressor can be reused.
Compressor Heaters
The compressor must be heated any time it is not running
to prevent refrigerant from condensing in the compressor.
The heaters are sized to maintain a minimum of 18°F or
20°F rise above the ambient temperature.
Two heaters are required: a cartridge type in the suction
end of the rotor housing and a band type on the muffler.
See
for heater details.