Installation
Low Ambient Damper Installation (SCIH only)
and follow the procedure below to install the low ambient damper option.
1.
Using a 1" hole saw, make a hole on the right side of the condenser fan discharge panel as
shown. Install a 1" bushing into the hole.
2. Apply the soft gasket material provided around the damper as shown.
3. Place the damper over the discharge opening using the screws (3/16 x 5/8") provided. See Detail
A.
4. Install the damper actuator, which was previously assembled to the mounting bracket, to the
right panel of the damper using the four screws (1/4 x 5/8") provided. Be sure the damper
actuator is in the closed position when installing.
5. Connect the capillary tube to the pressure operator using the flare fitting. Insert the tube
through bushing referenced in step 1. Route the capillary tube to the liquid line on circuit #1.
6. Remove the end cap from the access valve and attach to the end of the capillary tube.
Figure 9.
Low ambient damper installation
CIRC. #1C
IR
C
. #
1
CIRC. #2C
IR
C
. #
2
LIQUID LINE CIRCUIT #1
CONDENSER FAN DISCHARGE PANEL
1" HOLE
(FIELD OPERATION)
DETAIL "A"
SELF-DRILLING SCREW 3/16" X 5/8"
PROVIDED
SOFT GASKET
PROVIDED
installation procedure