 SXIH-SVX01C-EN

Installation

Pre-Startup Checklist

Complete this checklist after installing the unit to verify all recommended installation procedures 
are complete before unit startup. This does not replace the detailed instructions in the appropriate 
sections of this manual. Always read the entire section carefully to become familiar with the 
procedures.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper 
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to 
disconnect power before servicing could result in death or serious injury.

Receiving

Inspect unit and components for shipping damage. File damage claims immediately with 
the delivering carrier.

Check nameplate unit data so that it matches the sales order requirements.

Check unit for missing material. Look for ship-with accessories that are packaged separately 
and placed inside the access panel, fan section, or compressor section. See the 

“Receiving 

and Handling,” p. 9

 section.

Unit Location

Ensure the unit location is adequate for unit dimensions, ductwork, piping, and electrical 
connections.

Ensure access and maintenance clearances around the unit are adequate. See the 

“Service 

Access,” p. 10

 section.

Unit Mounting

Remove shipping brackets on the compressor assembly and supply fan.

Component Overview

Verify the fan and motor sheaves are aligned.

Check the belt tension for proper adjustment.

Ensure the fan rotates freely.

Tighten locking screws, bearing set screws and sheaves.

Ensure bearing locking collars do not wobble when rotated.

Ensure all air filters are properly installed with consideration of size and air flow.

Manually rotate the condenser and evaporator fans to ensure free movement. Verify that all of the 
fan mounting hardware is tight.

Ductwork

Verify that all ductwork conforms to NFPA 90A or 90B and all applicable local codes.

Startup

Содержание SCIH

Страница 1: ...October 2008 SXIH SVX01C EN Installation Operation Maintenance Integral Air Cooled Self Contained Unit Model SCIH SCIJ A0 and later design sequence...

Страница 2: ...Cs Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment our customers and the air conditioning industry All technicians who handle r...

Страница 3: ...gn sequences Note The procedures discussed in this manual should only be performed by qualified experienced HVAC technicians Note This document is customer property and must be retained by the unit s...

Страница 4: ...Plenum 14 Table 2 SCIH SCIJ Plenum Dimensions Weight in lbs 14 Figure 5 Low Ambient Damper 14 Table 3 SCIH SCIJ Low Ambient Damper Dimensions Weight in lbs 14 Figure 6 Hot Water Coil 15 Table 4 SCIH...

Страница 5: ...ce of Operation 26 Table 9 Normal Operating Conditions SCIH SCIJ 26 Table 10 Controls Adjustment SCIH SCIJ 26 Maintenance 27 Table 11 Integral Air Cooled General Data 27 Maintenance Procedures 27 Clea...

Страница 6: ...t 7 Heat Coil 0 none 1 5 ton hot water coil 2 7 5 ton hot water coil 3 10 15 ton hot water coil 4 5 ton steam coil 5 7 5 ton steam coil 6 10 15 ton steam coil Digit 8 Discharge Plenum 0 none 1 5 ton p...

Страница 7: ...pply air SZ single zone unit airflow VAV variable air volume Note Cross reference to related publication Internal Air Cooled Self Contained Product Catalog PKG PRC009 EN Refrigeration Circuits Units a...

Страница 8: ...tor and compressor and a 5 second delay timer Remote thermostat controls are field installed Field Installed Accessories These items ship separately for field installation steam coil hot water coil pl...

Страница 9: ...ion is level Receiving and Handling Shipping Package Integral air cooled units ship assembled on skids Units ship in the unitary configuration assembled piped and charged with refrigerant Receiving Ch...

Страница 10: ...sensitive Unit Location Install the unit in a dry indoor area between 50 and 115 F Choose a location where sound levels airflow and vibration commonly associated with heavy duty commercial equipment...

Страница 11: ...2 76 74 80 24 90 34 25 0 75 5 7 5 tons back view front view side view CONDENSER RETURN RETURN AIR SIDE ACCESS SIDE ACCESS SUPPLY AIR SUPPLY AIR CONDENSER DISCHARGE 31 50 13 64 2 74 Table 1 SCIH SCIJ u...

Страница 12: ...SS GRILL FORKLIFT ACCESS CONDENSER COIL 2 68 74 80 24 90 85 83 22 70 15 20 10 03 15 20 16 67 18 86 14 77 18 86 34 25 0 75 10 15 tons back view front view side view CONDENSER RETURN RETURN AIR SIDE ACC...

Страница 13: ...H SVX01C EN 13 Installation Figure 3 SCIH SCIJ component overview inlet filter frame airflow vent airflow airflow low ambient damper outlet water coil supply airflow supply airflow dimensions and weig...

Страница 14: ...num dimensions weight in lbs Unit Size A B C Grill Size W x H Weight 5 7 5 ton 56 16 31 52 x 12 95 10 15 ton 85 7 8 16 31 81 7 8 x 12 141 Figure 5 Low ambient damper Table 3 SCIH SCIJ low ambient damp...

Страница 15: ...nstalled 2 Coil connections are mirror image and can be mounted with either left or right hand connections Figure 7 Steam coil Table 5 SCIH SCIJ steam coil dimensions weights in lbs return supply Unit...

Страница 16: ...cts away from unit to protect unit from rain and snow entering with condenser air Auxiliary louvers and hoods may be required for this purpose Attach ducts to unit with canvas section duct connectors...

Страница 17: ...ements Size protection devices according to the electrical date on the unit nameplate 3 If using a field supplied disconnect install it at or near the unit in accordance with NEC Do not mount a field...

Страница 18: ...isconnect switch does not exceed 2 0 percent the imbalance is caused by faulty wiring within the unit Be sure to conduct a thorough inspection of the unit electrical wiring connections to locate the f...

Страница 19: ...tected power supply wiring to a field supplied installed disconnect and unit power terminal block or to the optional unit mounted disconnect switch Properly ground the unit Table 7 Integral air cooled...

Страница 20: ...ll end for end and bolt it to the support channels with the discharge towards the back Mounting holes are provided in the fan scroll 6 Align the fan and motor sheaves Install the belt and adjust the b...

Страница 21: ...s previously assembled to the mounting bracket to the right panel of the damper using the four screws 1 4 x 5 8 provided Be sure the damper actuator is in the closed position when installing 5 Connect...

Страница 22: ...lled for either right or left hand connections However steam coils must have the condensate lines connected to the bottom outlet with the top outlet capped 7 A heating coil control relay is factory pr...

Страница 23: ...rial provided completely around the top of the unit frame as shown in the detail drawing 3 Tighten the screws provided as shown Use screws on the rear right and left sides through the pilot holes on t...

Страница 24: ...ng material Look for ship with accessories that are packaged separately and placed inside the access panel fan section or compressor section See the Receiving and Handling p 9 section Unit Location En...

Страница 25: ...djust temperature setting to below room temperature The evaporator fan condenser fan s and compressor s should start Note These units are equipped with high efficiency scroll compressors Check for pro...

Страница 26: ...nd evaporator will operate on a signal from the thermostat calling for cooling With the fan switch set to Auto and the system switch set to Cool the following sequence takes place On a rise in room te...

Страница 27: ...all worn contacts Table 11 Integral air cooled general data Nominal Tons 5 7 5 10 15 ARI capacity btu h 65 000 91 000 121 900 177 200 EER 11 20 10 36 10 38 9 76 Refrigerant type circuit charge lbs R 4...

Страница 28: ...e to follow all safety instructions could result in death or serious injury To clean the refrigerant coil use a soft brush and sprayer such as a garden pump up or high pressure type In addition use a...

Страница 29: ...nt into containment When leak checking be aware of any new leak test methods which eliminate refrigerant as a trace gas When cleaning system components or parts do not use CFC11 R11 or CFC113 R113 Ref...

Страница 30: ...leaks when nitrogen is added 5 Retest the system to make sure new connections are solid 6 If a leak is suspected after the system has been fully charged with refrigerant use a halogen leak detector ha...

Страница 31: ...or if filters are dirty 2 Inspect coils for icing Icing on the coils may indicate low airflow supply restricted airflow from dirty fins 3 Check the fan belt condition and tension Adjust tension if bel...

Страница 32: ...ls if necessary 7 Compressor shorted open or burned 7 Check for shorts opens and grounded Remove and replace compressor 8 Defective compressor 8 Remove and replace Problem Remedy Unit held off by safe...

Страница 33: ...rge pressure with gauges If refrigerant is low recharge system 5 Overcharge of refrigerant indicated by high wattage and sweating of the compressor return line 5 Reclaim excess refrigerant 6 Thermosta...

Страница 34: ......

Страница 35: ......

Страница 36: ...e mail us at comfort trane com Literature Order Number SXIH SVX01C EN Date October 2008 Supersedes SXIH SVX01C EN June 2008 Trane has a policy of continuous product and product data improvement and r...

Отзывы: