Trane RAUT 250 Скачать руководство пользователя страница 10

10

RAUT-IOM-R410A

Installation

Refrigerant charging

After the refrigeration pipework system has been pressure
tested and evacuated, and meets the vacuum pressure
requirements of paragraph <<Field evacuation>>, the
refrigerant may be charged as follows. Be sure to follow the
start-up procedure at the same as charging the refrigerant.
1. Loosely connect a cylinder of refrigerant to the 1/4” OD
    Charging Valve Located on the liquid line.
2. Open and close the valve on the refrigerant cylinder to
    purge the connection. Tighten the coupling nut.
3. Invert the refrigerant cylinder so that only liquid will enter
    the system
4. Allow the compressor to continue running throughout the
    remainder of the charging operation. Do not allow the
    pressure to fall bellow 0.15 bar.

     Caution

:

     Do not attempt to start the compressor by blocking  the
     safety controls. Allow  the condensing unit to function
     in a normal manner.

5. Allow the system  to continue functioning for approximately
    30 minutes. If during this period bubbles appear in the
    liquid line sight glass, add refrigerant.
6.Leak-test the refrigerant circuit.

Start-up procedure

Refrigerant charge

1. Start the unit by switching to <<On>>
2. After the unit has started, allow it to operate for at least
   15 minutes to stabilise operating pressures. Then check :
        - compressor oil level.
        - compressor and fan motor power consumption.
        - suction pressure.
        - discharge pressure.
        - liquid line sight glass.
        - superheat.
        - subcooling.
All readings and measurement should be logged.
Procedures are given below.

Maximum

oil level

Minimum

oil level

               WARNING

1. Do NOT run the compressor on reverse rotation
2. Do NOT perform any pump down cycle with Scroll
    compressor
3. Do Not  run the compressor below the  setting of low
    pressure switch
4. Do NOT by pass any safety devices when operating the
    system.
Failure  to observe any of the  above  will cause severe
damage to the  Scroll compressors.

Oil level

Oil should be visible in the compressor, under full load, in
the compressor oil level sight glass. The unit was  charged
with the proper  amount of oil before shipping. Under normal
 operation, compressor oil is always expected to  return to
compressor oil sump, and no additional oil should be added.
For oil level indication, refer to compressor oil sight glass, as
per Figure 3 . If oil is within sight glass visibility, oil quantity
should be sufficient.

Refrigerant pressures

Observe operating pressures. If  pressures are above or
below normal see <<Trouble Analysis>> section. Normal
operating pressures are in Table 2.  A High & Low pressure
settings are found in Table 1

Liquid line sight glass (Optional)

The flow of   refrigerant through the sight glass should be
smooth and  without bubbles. Bubbles indicate a refrigerant
shortage and probably a leak, or a restriction  in the liquid
line.

Superheat

Normal  Superheat  is  6  to  8  deg  C.  Overfeeding  of   the
evaporator results in high suction pressure, low superheat
and possible liquid carryover. Inadequate  or too high a
superheat is remedied by adjusting stem on the  thermostatic
expansion valve (TEV). If this fails to correct  the  condition,
then the valve  cage or power element of  the  TEV may be
defective and should be replaced.

  Caution:

  1.  Excessive  foaming  indicates  the  presence  of
        refrigerant in the oil and will result  insufficient
        compressor lubrication. Turn off the motor and
        investigate the cause.
  2.  An excess of  the oil in the compressor can cause
         problems in the same way as a lack of oil. Before
         topping up , contact a qualified service technician.
         Use only Tranerecommended oils.

Figure 3  - Compressor oil level

                CAUTION

        PHASE ROTATION IS CRITICAL

IF SUCTION PRESSURE DOSE NOT FALL TO EXPECTED
OPERTATING  LEVEL  WITHIN  THIRTY  (30)  SECONDS
AFTER  COMPRESSOR  IS  STARTED,  COMPRESSOR
ROTATION MAY BE REVERED.

TO REVERSE ROTATION, DISCONNECT ALL UNIT POWER
AND REVERSE ANY TWO (2) INCOMING POWER LEAD
WIRES AT THE UNIT HIGH VOLTAGE TERMINAL BLOCK.
 RECONNECT ALL UNIT POWER, RESTART UNIT, AND
RE-CHECK SUCTION PRESSURE.

Note :  

R-410A refrigerant charge must be liquid phase only.

Liquid pressure

Liquid

Line

Suction

Line

Suction pressure

R-410A

Bottom tank

Содержание RAUT 250

Страница 1: ...n be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equi...

Страница 2: ...No 11 Minor Major Design Sequence Comp Motor A Modular RAUT Design Digit No 12 Factory Installed 0 No Option A Corrosion Resistant Coated Fin Blue Fin B Hydrophobic Coating Fin C Copper Fin and Coppe...

Страница 3: ...Contents Model Nomenclature System Precaution General Information General Data Installation Operation Maintenance Maintenance Compressor Trouble Analysis Dimensional Data Electrical Wiring 2 4 5 6 7 1...

Страница 4: ...ing leakage of water etc Be sure to cut off the main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electri shock Any presence of foreign substan...

Страница 5: ...mail Notify the local Trane Sales Office Concealed damage must be reported within 15 days delivery Check the unit nameplate to confirm that the proper unit was shipped Available power supply must be c...

Страница 6: ...00 26 100 29 000 49 500 29 000 49 500 Vendor Motor Type 710W 710W 900W 1800W 1800W Qty 2 2 2 2 2 Speed RPM 920 920 920 720 720 V ph Hz 380 3 50 380 3 50 380 3 50 380 3 50 380 3 50 RLA LRA each A 3 22...

Страница 7: ...le of handling the weight of the unit Table 1 Clearances Provide sufficient clearance around the unit for performance of service and maintenance Caution unit operation is a function of the air tempera...

Страница 8: ...t and dry nitrogen for leak testing a violent explosion may result 3 Always use a pressure regulator valves and gauges to control drum and line pressures when pressure testing the system Excessive pre...

Страница 9: ...ety 2 Use copper conductors only for installation wiring Unit terminals are not designed to accept other type of wiring The use of aluminium wire may cause galvanic corrosion and or overheating at the...

Страница 10: ...er full load in the compressor oil level sight glass The unit was charged with the proper amount of oil before shipping Under normal operation compressor oil is always expected to return to compressor...

Страница 11: ...e 3B EXPANSION VALVE CAPILLARY TUBES SIGHT GLASS STRAINER LIQUID LINE FROM RECEIVER EXPANSION VALVE SOLENOID LIQUID VALVE EXPANSION VALVE EXPANSION VALVE THERMAL BULBS EXPANSION VALVE EQUALIZER LINES...

Страница 12: ...recommended procedures The following procedures should be carried out by a qualified service technician as part of a maintenance contract The first and last visit will include the seasonal shut down...

Страница 13: ...ction filter is required install it a minimum of 18 upstream of the compressor manifold piping See Figure 4 Caution Altering the original manifold piping may cause oil compressor failure This sequence...

Страница 14: ...line but not on motor side or fuse Voltmeter does not read proper voltage Motor starter holding coil is not energized Compressor will not operate Open contact on high pressure switch Discharge pressu...

Страница 15: ...obable cause Insufficient oil charge Clogged filter drier Liquid flooding back to compressor Recommended action All oil Replace Readjust superheat setting and verify correct bulb mounting F Compressor...

Страница 16: ...Expansion valve opens too far a Adjust superheat and check flood back to compressor bulb attachment b Expansion valve stuck in open b Repair or replace position L Discharge pressure too high Problems...

Страница 17: ...00 1693 0 222 2 208 0 67 4 146 7 SUCTION CONNECTION 1 5 8 1786 0 LIQUID CONNECTION 5 8 99 5 1588 0 99 5 RECOMMANDED CLEARANCE 1070 821 0 RECOMMANDED CLEARANCE 1524 RECOMMANDED CLEARANCE 1524 RECOMMAND...

Страница 18: ...273 0 273 0 2206 0 1156 0 2380 3 RECOMMANDED CLEARANCE 1070 RECOMMANDED CLEARANCE 1524 464 0 183 0 578 0 297 1 128 0 SUCTION CONNECTION SIZE 1 5 8 LIQUID CONNECTION SIZE 5 8 RECOMMANDED CLEARANCE 152...

Страница 19: ...RAUT IOM R410A 19 Electrical Wiring RAUT250 400 Micro P 1 2...

Страница 20: ...20 RAUT IOM R410A Electrical Wiring RAUT250 400 Micro P 2 2...

Страница 21: ...RAUT IOM R410A 21 Electrical Wiring RAUT500 600 Micro P 1 2...

Страница 22: ...22 RAUT IOM R410A Electrical Wiring RAUT500 600 Micro P 2 2...

Страница 23: ...RAUT IOM R410A 23 Electrical Wiring RAUT250 400 with Carel pCO5 1 2...

Страница 24: ...t 1 ID10 J7 2 Low Pressure Switch Circuit 2 ID11 J7 3 High Pressure Switch Circuit 2 ID12 J7 4 Compressor 1 Overload Circuit 2 IDC9 J7 5 Common DI 9 12 ID13h J8 1 Not used ID13 J8 2 Compressor 2 Overl...

Страница 25: ...RAUT IOM R410A 25 Electrical Wiring RAUT500 600 with Carel pCO5 1 2...

Страница 26: ...t 1 ID10 J7 2 Low Pressure Switch Circuit 2 ID11 J7 3 High Pressure Switch Circuit 2 ID12 J7 4 Compressor 1 Overload Circuit 2 IDC9 J7 5 Common DI 9 12 ID13h J8 1 Not used ID13 J8 2 Compressor 2 Overl...

Страница 27: ...RAUT IOM R410A 27 Note...

Страница 28: ...ations without notice We are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor env...

Отзывы: