Tank Replacement

The contents of this canister must 

be reclaimed at a Trane authorized 

facility. Disposal of the canister or 

the contents in any other way may 

be a violation of Federal CFC/

HCFC Venting Regulations.

Warning!

!

The saturation level of the activated carbon in the canister is directly related 
to the accumulated pump out time on the Purifier Purge. When the pump out 
time on the Purifier Purge timer reaches the value listed in line “A” or the 
date on line “B” of the Change Purifier Plus™ Canister label (Figure 4) the 
carbon is saturated and the canister needs to be replaced.

The most accurate way to determine if a canister needs replacement is to 
weigh the cylinder. The tare weight of the carbon tank and carbon is con-
tained on a sticker on the bottom of the carbon tank (sometimes located 
elsewhere on the tank). The weight is listed as pounds-ounces. For example 
42-10 means 42 lbs. 10 ounces.    

The amount of refrigerant that can be held within a given quantity of acti-
vated carbon depends on many variables including the carbon type, refriger-
ant type, as well as the temperature and pressure of the carbon. At typical 
equipment room temperatures the Purifier Plus canister will hold approxi-
mately 12 lbs of refrigerant.   

If the current tank weight is any more than 6 lbs. over the tare weight listed 
on the label, it is time to exchange the tank. In the above example, any 
weight over 48 lbs 10 ounces (42 lbs. 10  6 pounds = 48 lbs. 10 
ounces) should be exchanged. There is no problem in exchanging a tank at 
a weight between 0 and 6 lbs. over the tare weight, however.

Removing the Old Canister

The refrigerant vapor in the purge exhaust line can be pumped into the can-
ister before removing the copper lines by:

1. Disconnect and plug the ¼” line entering the pump out compressor.
2. Remove the bypass cap from the pump out compressor inlet tee and turn 

on the pump out system using the purge service switch for ten to fifteen 
seconds. This will pull room air into the pump out compressor and force 
purge exhaust into the Purifier Plus canister.

3. Disconnect the copper lines from the full canister and cap the inlet and 

outlet ports of the canister.

4. Install replacement tank and update all label information per steps 4 and 

5 of the “Installation” section of this manual.

5. Reconnect the tubing and replace the cap removed in Steps 1 and 2 of 

this section.

Содержание Purifier Plus Purge

Страница 1: ...PRG IOM 3E Installation Operation Maintenance Purifier Plus Purge Emission Collection Canister...

Страница 2: ...on 3 Model Number Description 3 Warnings and Cautions 4 Literature History 4 About this Manual 5 Receiving 5 Installation 7 Tank Replacement 9 Return Instructions 10 Maintenance 11 Specifications 11 D...

Страница 3: ...4 Development Sequence A First Development Digit 5 6 Future Use Digit 7 Tank Origin 0 Trane 1 Out source Digit 8 Tank Type N New R Regenerated Digit 9 Refrigerant 1 R11 2 R123 3 R113 4 Generic R11 R1...

Страница 4: ...Manual revised to include Updated canister drawing PRG IOM 3D October 1998 Manual revised to include Deletion of Hazardous shipping form information Added Pressurized Tank Warning PRG IOM 3E October...

Страница 5: ...ges Use with other purges may result in a potential safety hazard and or damage to the purge due to partial restriction of the purge exhaust Receiving Upon receipt of the unit inspect the shipping car...

Страница 6: ...ts 3 8 OD refrigeration grade copper tubing Length determined by location of canister 4 Bolts Use when canister is bolted directly to chiller such as Option 3 in Figure 2 Figure 1 Purifier Plus Canist...

Страница 7: ...valves are included in the line they must be fully open during use 4 Install or modify the Change Purifier Plus Canister label Figure 4 on the Purifier Purge near the minute timer Add the applicable...

Страница 8: ...pump out timer value at installation plus appropriate value from Table 1 B Installation date plus 3 years Figure 5 Typical Unit Nameplate Order No Example Model No PRPA000N2A0 Serial No L93C02684 For...

Страница 9: ...the temperature and pressure of the carbon At typical equipment room temperatures the Purifier Plus canister will hold approxi mately 12 lbs of refrigerant If the current tank weight is any more than...

Страница 10: ...onfirm the items listed under replacement canister were received 2 Document It Record all information on the data sheet enclosed in this IOM and or on tank labels and return the completed sheet with t...

Страница 11: ...ize Including bracket 21 H X 13 W X 14 L Connection sizes Inlet 3 8 Male flare Outlet 3 8 Male flare Temperature Range Operating 40 to 120 F Shipping and Storage 40 to 150 F DO NOT PAINT THE TANK The...

Страница 12: ...Empty Weight of Cylinder from sticker on bottom of tank Refrigerant type Chiller Model Number 1st 12 digits Chiller Serial Number Chiller Sales Order Number Tank Order Number or N A From Nameplate Tan...

Страница 13: ...SV CAP PP PRG IOM 3E 1001 Supersedes PRG IOM 3D Stocking Location La Crosse The Trane Company Aftermarket Business Unit 3600 Pammel Creek Road La Crosse WI 54601 www trane com An American Standard Com...

Отзывы: