Clearances
illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged unit
capacity, and peak operating efficiency. Providing less than
the recommended clearances may result in condenser coil
starvation, “short-circuiting” of exhaust and economizer
airflows, or recirculation of hot condenser air.
Figure 24.
Typical installation clearances for single and multiple unit applications
Side by Side
Note 1
End to End
Note 1, 2
7’0”
2134 MM
6’0”
1829 MM
3’0”
914 MM
Single Unit
3’0”
914 MM
3’0”
914 MM
4’0”
1219 MM
Notes:
1. When equipped with economizer
or barometric relief damper, clearance
distance is to be measured from
protruding hood instead of base.
2. Clearance is the same if any unit
is rotated 180 degrees.
4’0”
1219 MM
for D cabinet
5’0”
1525 MM
for D cabinet
5’8” for D cabinet
1727 MM
Weights
Table 1.
Model weights, corner weights (lbs) and center of gravity dimensions (in.)
Tons
Unit Model No.
Model Weights
(a)
Corner Weights
(b)
Center of Gravity (in.)
Shipping
Net
A
B
C
D
Length
Width
6
THJ072
1007
909
298
278
160
172
43
19
7.5
THJ090
1011
913
300
280
161
172
43
19
8
THJ102
1027
929
305
285
164
176
43
19
10
THJ120
1037
939
308
288
165
177
43
19
12.5
THJ150
1412
1218
356
360
252
250
50
26
15
THJ180
2040
1820
611
447
322
440
52
36
17.5
THJ210
2070
1850
612
463
334
441
53
36
20
THJ240
2140
1920
689
472
309
451
50
34
25
THJ300
2190
1970
684
484
332
469
51
35
(a)
Weights are approximate. Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights to be added to unit weight,
reference the following table.
(b)
Corner weights are given for information only.