Installation
28
RT-SVX22J-EN
Note:
Check to insure that the flexible tubing lies flat on
the base pan surface.
4. Slide the top bracket down the copper sensing tube.
For TSC036E-060E, and THC036-037E units insert the
tab on the left side into the slot on the indoor coil block
off and secure the right side of the bracket with one of
the 3 screws removed in step 2. Refer to
Figure 33,
p. 27
. For THC047E-120E, THC048F-092F, and TSC072F-
120F units secure the tab on left side to the indoor coil
block off with one of the screws removed in step 2 and
secure the right side of the bracket with one of the
screws removed from the access panel. Refer to
Figure 34, p. 28
.
5. Using the remaining 2 screws removed in step 2,
secure the bottom bracket. Refer to
Figure 33, p. 27
.
Note:
Larger diameter holes on bottom bracket line up
with the dimples on the rear panel. The smaller
diameter holes line up with the screw holes in the
rear panel.
Main Electrical Power Requirements
Failure to follow this instructions could result in death or
serious injuries.
Verify that the power supply complies with the unit
nameplate specifications.
•
Inspect all control panel components; tighten any
loose connections.
•
Connect properly sized and protected power supply
wiring to a field-supplied/installed disconnect switch
and to the main power terminal block (HTB1) in the unit
control panel.
•
Install proper grounding wires to an earth ground.
Electric Heat Requirements
•
Verify that the power supply complies with the electric
heater specifications on the unit and heater nameplate.
•
Inspect the heater junction box and control panel;
tighten any loose connections.
•
Check electric heat circuits for continuity.
Low Voltage Wiring
(AC & DC) Requirements
•
Install the zone thermostat, with or without switching
subbase.
•
Connect properly sized control wiring to the proper
termination points between the zone thermostat and
the unit control panel.
Condensate Drain Configuration
An evaporator condensate drain connection is provided
on each unit. Refer to
Figure 16, p. 21
and
Figure 17, p. 22
for the appropriate drain location.
The condensate drain pan is factory installed to drain
condensate to the back side of the unit. See
Figure 16, p. 21
and
Figure 17, p. 22
. It can be converted to drain
condensate out the front side of the unit or through the
base.
To convert drain condensate out the front of unit:
1.
Remove evaporator access panel and supply air access
panels.
Figure 34.
Horizontal view 2
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged. Failure to
disconnect power and discharge capacitors before
servicing could result in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
4
2
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Содержание Precedent THC036E
Страница 37: ...Installation RT SVX22J EN 37 Figure 51 Examples...
Страница 63: ......