Table 15 - Data Point List for CVGE/CVAE/RTHC chillers, UCP2 controller
Data
Type
Offset
Point Description
Function
Modbus
Index
00002
1
Tracer Chiller Auto/Stop (1 = auto, 0 = stop)
bit
40001
0
Tracer Chilled Water Setpoint
Temperature
40002
1
CTV/RTH: Tracer Current Limit Setpoint
Percentage
40003
2
Copy of function 5/15 binary points
bitfield
Bit 0 CTV: Hot Gas Bypass (1 = On, 0 = Off)
Bit 1 CTV: Free Cooling Mode Request (1 = On, 0 = Off)
Bit 2 CTV: Water Temp Control Mode Request (1 = Heat, 0 = Cool)
Bit 3 UNUSED
Bit 4 CTV/RTH/ABS: Base Load Mode Request (1 = yes, 0 = no)
Bit 5 CTV/RTH: Ice Making Mode Request (1 = yes, 0 = no)
Bit 6 RESERVED
Bit 7 Tracer Chiller Auto/Stop (1 = auto, 0 = stop)"
bitfield
40005
4
CTV: Tracer Hot Water Setpoint
Temperature
40006
5
CTV/RTH: Tracer Ice Termination Setpoint
Temperature
10001
0
Compr/Unit Running (1 = Yes, 0 = No)
bit
10002
1
Chilled Water Flow (1 = On, 0 = Off)
bit
10003
2
Condenser Water Flow (1 = On, 0 = Off)
bit
10004
3
MMR exits
bit
10005
4
MAR exits
bit
10006
5
Equipment communication
bit
10007
6
Compr/Unit Running (1 = Yes, 0 = No)
bit
10012
11
Remote Setpoints Valid(1 = Yes, 0 = No)
bit
10013
12
UCM Power Loss has occurred (1 = Yes, 0 = No)
bit
10014
13
No_TCI4_UCM_Com (1=no com)
bit
10015
14
Alarm (1 = On, 0 = Off)
bit
10016
15
Condenser Water Pump (1 = On, 0 = Off)
bit
10017
16
Chilled Water Pump (1 = On, 0 = Off)
bit
10018
17
Limit Warning (1=Warning)
bit
10019
18
CTV/ABS: Max Capacity (1 = Yes, 0 = No)
bit
10020
19
Reset Relay (1 = On, 0 = Off)
bit
10021
20
CTV/RTH: Actively Ice Making (1 = Yes, 0 = No)
bit
10022
21
IFW exists
bit
10023
22
ABS: Rfgt Flow (1 = No Flow)
bit
10024
23
ABS: PCL Switch Status
bit
10025
24
CTV/RTH: Ice Machine Control
bit
10026
25
CTV: Hot gas bypass status
bit
10027
26
CTV: Heat pump status
bit
10028
27
CTV: Free cooling status
bit
10029
28
CTV/RTH/ABS: Base loading status
bit
10030
29
Chiller mode
bit
10031
30
CTV: Condensor fan 1
bit
10032
31
CTV: Condensor fan 2
bit
10033
32
CTV: Condensor fan 3
bit
10034
33
CTV: retired for Tracer (Cond. fan 4)
bit
10035
34
CTV: Oil pump relay
bit
Binary
Outputs
5/15
Analog
Outputs
6/16
Binary
Inputs
2