These

 

instructions

 

cover

 

installation

 

of

 

ICM Part No.325-HN on all split system heat pumps. The device is designed to control outdoor 

fan motor speed under low outdoor temperature conditions. It is specifically designed to control condenser fan motor speed in reponse 
to the saturated condensing temperature during operation in cooling mode only.

This kit is not applied on the units with ECM fan motor

.

Parts necessary for mounting control and sensor assembly are included in the kit. Either assembly can be replaced independently of the 
other.

STEP 1- Be certain power to unit is disconnected.

STEP 2- Route sensor wire through the knockout on side plate then the right hole on E-part box

 

and over to outside row of coil (left 

side), be careful not to harm tubing (Figure 1).

STEP 5- Bind unused wire and secure it near or next to control.

STEP 6- Protect sensor wire from physical damage or wind movement where necessary.

Note

: Wiring in field installed, an insulated sleeve that meets local laws and regulations must be added to protect the wires.

Figure 3

Figure 2

Sensor

Figure 1

STEP 4- Secure sensor on the condenser coil found in STEP 2 
with the belt supplied.

Note: The sensor is delicate. Handle with care.

STEP 3- Find the coil return bend as shown in Figure 2 on which 
sensor will be mounted.

Top of coil

Top of coil

E-part box

See detail A

Side plate

Detail A

The right hole

The knockout 

2

 

Introduction

Mounting sensor