background image

SS-APG008H-EN

5

Overview

Trane’s TTA and TWA, 6 – 25 ton condensing unit product
line (specific model numbers are listed on the cover) has
been designed for use only with R-410A and POE oil. R-
410A is a higher pressure refrigerant that requires the other
components of the system to be rated for the higher
pressures. For compressor lubrication, the refrigerant
requires POE oil.

Traditionally, refrigerant piping practices were guided by
four principles:

Return the oil to the compressor.

Maintain a column of liquid at the expansion valve.

Minimize the loss of capacity.

Minimize the refrigerant charge in the system.

These piping practices remain the same. However,
because of the different mass flows and pressures, the line
diameter required to carry the oil and refrigerant may not
be the same as a similar tonnage R-22 unit. Also, the
allowable pressure drop may be greater for R-410A than R-
22.

Evidence accumulated over years of observation
demonstrates that the lower the refrigerant charge, the
more reliably a split air-conditioning system performs. Any
amount of refrigerant in excess of the minimum design
charge becomes difficult to manage. The excess refrigerant
tends to collect in areas that can interfere with proper
operation and eventually shortens the service life of the
system. To successfully minimize the system refrigerant
charge, the correct line size should be used and the line
length must be kept to a minimum.

Background

In a split air-conditioning system, the four major
components of the refrigeration system are connected by
field-assembled refrigerant piping. A vapor or gas line
connects the evaporator to the compressor, the discharge
line connects the compressor to the condenser, and the
liquid line connects the condenser to the expansion device,
which is located near the evaporator inlet. Operational
problems can occur if these refrigerant lines are designed
or installed improperly.

Figure 1.

Interconnecting refrigerant lines in a typical

split air-conditioning system

vapor or gas

line

The origin of the requirements for equivalent line lengths of
components, line pressure drop, and minimum and
maximum refrigerant velocities is uncertain. It appears
likely that at least some of the supporting data was derived
from measurements and/or equations involving water.
Some resource materials even show water components
when illustrating refrigerant piping requirements.

Subsequent reviews of analytical and empirical data for
refrigerant piping resulted in the publication of two research
papers:

Pressure Losses in Tubing, Pipe, and Fittings

by R.

J.S. Pigott and

Refrigerant Piping Systems — Refrigerants

12, 22, 500

by the American Society of Refrigeration

Engineers (ASRE). In his paper, Pigott described his use of
refrigerant as the fluid and his direct measurement of
pressure drops. His findings indicated that the pressure
drop of many line components is small and difficult to
measure. For these components, he used experimental
data to derive a formula relating the geometry of the
component to its pressure drop. Overall, his calculated
pressure loss of the components was less than originally
determined.

The conclusion of the ASRE research paper stated that the
minimum required velocity to maintain oil entrainment in
vertical risers and horizontal lines will vary with the
diameter of the tube and with the saturation temperature of
the suction gas. In other words, the minimum required
velocity for oil entrainment is not constant.

Updated Guidelines

Liquid Lines

Historically, liquid lines were sized to minimize the pressure
losses within the piping circuit. Oil movement through the
piping wasn’t a concern (nor is it today) because oil is
miscible in liquid refrigerant at normal liquid-line
temperatures. The historic and traditional 6 psid liquid line

Содержание Odyssey TTA0724 A Series

Страница 1: ...person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment June 2022...

Страница 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Страница 3: ...itutes or refrigerant additives WARNING Explosion Hazard Failure to follow instructions below could result in an explosion which could result in death or serious injury and equipment damage NEVER bypa...

Страница 4: ...g Routing and Component Selection 9 Liquid Lines 9 Line Sizing 9 Routing 9 Insulation 9 Components 9 Gas Line 10 Line Sizing 10 Routing 10 Insulation 11 Components 11 Expansion Valves 12 Controls 13 H...

Страница 5: ...r the evaporator inlet Operational problems can occur if these refrigerant lines are designed or installed improperly Figure 1 Interconnecting refrigerant lines in a typical split air conditioning sys...

Страница 6: ...equation based formulas to predict the entrainment velocities of R 410A refrigerant and POE oil These minimum velocities are reflected in the line sizes listed in the component selection summary table...

Страница 7: ...contact the manufacturer for review Figure 3 Allowable elevation difference TWA above indoor unit Not allowed for TWA units Note Regardless of orientation hot gas bypass HGBP lines are limited to 75...

Страница 8: ...nits Note Route refrigerant piping for minimum linear length minimum number of bends and fittings Important Read Application Guide SS APG008 EN thoroughly before installing this unit Note All liquid p...

Страница 9: ...or positioning the components in the liquid line Position the components as close to the indoor unit as possible The Component Selection tables found in Parts p 25 identify suitable components by part...

Страница 10: ...th Refrigerant Line Failure to follow instructions could cause a refrigerant line to explode under pressure which could result in death or serious injury Liquid refrigerant trapped between two valves...

Страница 11: ...promotes stable TXV operation Avoid Underground Refrigerant Lines Underground lines create risk due to refrigerant condensation during the off cycle installation debris inside the line including conde...

Страница 12: ...nsure the condensing unit is capable of operating at these conditions Example 2 10 ton coil one refrigerant circuit with two distributors and a 60 40 coil split 10 x 6 6 and 10 x 4 4 One TXV should be...

Страница 13: ...to the third party Simply stated this means that when a compressor turns on it shouldn t turn off until the expansion valve comes under control And once the compressor turns off it should be allowed...

Страница 14: ...g applications To prevent evaporator freeze up our equipment typically includes Trane Frostat coil frost protection Like hot gas bypass the Frostat system protects the coil from freezing but it does s...

Страница 15: ...OD and smaller of type L copper are suitable for use with R 410A Suction lines 3 1 8 OD must use type K or thicker wall Discharge lines liquid lines heat pump vapor lines and hot gas bypass lines 1 3...

Страница 16: ...enters the coil quickly turns to liquid The MCHE tube volume holds very little refrigerant so the refrigerant charge of the system is reduced However the tube volume is so small that if the flow of re...

Страница 17: ...are a field installed option and no longer come standard from the factory Figure 8 TTA cooling only unit and matched indoor coil typical arrangement Notes 1 If the total length of the liquid line exce...

Страница 18: ...1 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liquid line filter driers from the TWA heat pump and install new f...

Страница 19: ...and one check valve See Table 3 p 26 and for recommendations 2 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liqui...

Страница 20: ...s away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction heade...

Страница 21: ...10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction header conditions See Line Sizing Routi...

Страница 22: ...xpansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is...

Страница 23: ...e for each expansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil by 1 inch per 10 feet 1 cm per 3 m 4 Use the DETINT to prevent oil and refrigerant migration when...

Страница 24: ...m 4 Use the DETINT to prevent oil and refrigerant migration when the unit is off The DETINT also serves to isolate the TXV bulb from suction header conditions See Line Sizing Routing and Component Se...

Страница 25: ...Unit TTA1804 D TTA1804 C TTA2404 D TTA2404 C TTA3004 C Refrigerant ckts 2 1 Manifold 2 1 Manifold 1 Manifold Minimum step tons 7 5 8 6 13 4 10 12 5 GAS LINE Tube diameter in Horizontal drops 1 1 8 1...

Страница 26: ...products require two filters and two check valves one set oriented for liquid in the cooling direction and one set oriented for liquid in the heating direction For units with line lengths in excess o...

Страница 27: ...urated at 90 F Discharge Saturated at 125 F Note When calculating refrigerant charge the first step is to determine the unit charge and if the unit charge includes the first 25 foot of pipe This infor...

Страница 28: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications...

Отзывы: