14
Warning:
• Please turn off the main power supply when servicing. And do not touch the B1, B2
terminals when the power is energized. If isolator should be used between outdoor
unit and branch box/indoor unit and branch box, please use 3-pole type or 2-pole type.
(Please refer to figure below.)
• Turn on the main power when the ambient temperature is -20°C (-4°F) or higher.
• Under conditions of -20°C (-4°F), it needs at least 4hr stand by before the units
operate in order to warm the electrical parts.
Caution:
After using the isolator, be sure to turn off and on the main power supply to reset the system. Otherwise, the outdoor unit may not be able to detect the branch
box(es) or indoor units.
Be sure to connect the outdoor-branch box/indoor-branch box connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the intermediate connection point.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)
Never splice the power cable or the indoor-outdoor-branch box connection cable, otherwise it may result in a smoke, a fire or communication failure.
B1
B2
L1
L2
Outdoor unit
2 poles isolator (Switch)
Branch box
7. Electrical work
Indoor unit
Type
V1
V2
NTXAMT
✱✱
A112A
✱
5
26.9
2.4
NTXCKS
✱✱
A112A
✱
1
17.1
2.4
NTXDKS
✱✱
A112A
✱
2
19.8
2.4
NTXFKS
✱✱
A112A
✱
3
7.4
2.4
NTXUKS
✱✱
A112A
✱
6
9.9
2.4
NTXWPH
✱✱
A112A
✱
4
6.8
2.4
NTXWST
✱✱
A112A
✱
3
7.4
2.4
PEAD-A
✱✱
AA
✱
5
26.9
2.4
PLA-A
✱✱
EA
✱
2
19.8
2.4
Branch box (
TAC-MKA
✱✱
BC
)
7
5.1
3.0
C : Multiple of tripping current at tripping time 0.01 s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
* Condition Branch Box × 2 +
PLA-A
✱✱
EA
✱
× 5, C = 8 (refer to right sample chart)
F2 = 5.1 × 2/8 + 19.8 × 5/8
= 13.65
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type 1) + V2 × (Quantity of Type 2) + · · · + V2 × (Quantity of Type 7) + V3 × (Wire length [km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
V3
1.5 mm
2
, AWG14
48
2.5 mm
2
, AWG13
56
4.0 mm
2
, AWG11
66
6000
600
60
10
1
1
2
3 4
6 8
C
10
20
SAMPLE
Sample chart
Rated Tripping current (x)
Tripping T
ime
[s]
0.1
0.01
Thickness of Wire for Main Power Supply and On/Off Capacities
Model
Power Supply
Minimum Wire Thickness
(mm
2
[AWG])
Breaker for
Wiring
*1
Breaker for Current
Leakage (if you use)
Minimum
circuit ampacity
Maximum rating of
over current protector
device
Main Cable
*2
Ground
Outdoor Unit
NTXMMX60A182A
✱
208/230 VAC, 60Hz 13.3 [AWG6]
13.3 [AWG6]
50 A
50 A 30 mA 0.1 sec.
or less
46 A
52 A
Indoor Unit
208/230 VAC, 60Hz
Refer to installation manual of indoor unit.
*1. Please follow applicable federal, state, or local codes to prevent potential leakage/electric shock. Or install a ground fault interrupt for the prevention of leakage and
electric shock.
IMPORTANT
If a current leakage breaker is used, it should be compatible with higher harmonics as this unit is equipped with an inverter. The use of an inadequate breaker
can cause the incorrect operation of inverter.
*2. Use copper supply wires. Use the electric wires over the rating voltage 300 V.
Total operating current of the indoor unit
Minimum wire thickness (mm
2
/AWG)
Ground-fault interruper
*1
(if you use)
Local switch (A)
Breaker for wiring
(NFB)
Main Cable
Branch
Ground
Capacity
Fuse
F0 = 15A or less
*2
2.1/14
2.1/14
2.1/14
15 A current sensitivity
*3
15
15
15
F0 = 20A or less
*2
3.3/12
3.3/12
3.3/12
20 A current sensitivity
*3
20
20
20
F0 = 30A or less
*2
5.5/10
5.5/10
5.3/10
30 A current sensitivity
*3
30
30
30
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + · · · + {V1 × (Quantity of Type 7)/C}
1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57). For exam
-
ple, use wiring such as YZW.
6. Install an earth longer than other cables.
RG79F381H02_EN.indd 14
2018/09/04 9:33:08