Trane Mitsubishi Electric NTXMMX20A122A Series Скачать руководство пользователя страница 6

En-5

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes and the 

pipe connections of the outdoor unit.

2) Align the center of the pipe with that of the pipe connections of the outdoor unit, 

then hand tighten the flare nut 3 to 4 turns.

3) Tighten the flare nut with a torque wrench as specified in the table.

•  Over-tightening may cause damage to the flare nut, resulting in refrigerant 

leakage.

•  Be sure to wrap insulation around the piping. Direct contact with the bare piping 

may result in burns or frostbite.

3-3. INSULATION AND TAPING

1) Cover piping joints with pipe cover.

2) For outdoor unit side, surely insulate every piping including valves.

3) Using piping tape (E), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (E) with tape (with adhesive agent attached).

•  When piping have to be arranged through above ceiling, closet or where the 

temperature and humidity are high, wind additional commercially sold insulation 

to prevent condensation.

 WARNING

When installing the unit, securely 

connect the refrigerant pipes before 

starting the compressor.

 CAUTION

When there are the ports which are 

not used, make sure their nuts are 

tightened securely.

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Tilted Uneven Burred

Good

No good

Burr

Copper pipe

Spare reamer

Pipe cutter

Smooth all 

around

Even length 

all around

Inside is shin-

ing without any 

scratches.

B

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Copper 

pipe

Pipe diameter  

[inch (mm)]

[inch (mm)]

A [inch (mm)]

Tightening torque

Clutch type tool for R410A Clutch type tool for R22

Wing nut type tool for R22

ft-Ib

N•m

kgf•cm

1/4 (ø6.35)

21/32 (17)

0 to 0.02

(0 to 0.5)

0.04 to 0.06

(1.0 to 1.5)

0.06 to 0.08

(1.5 to 2.0)

10 to 13

13.7 to 17.7

140 to 180

3/8 (ø9.52)

7/8 (22)

25 to 30

34.3 to 41.2

350 to 420

1/2 (ø12.7)

1-1/32 (26)

0.08 to 1.0

(2.0 to 2.5)

36 to 42

49.0 to 56.4

500 to 575

5/8 (ø15.88)

1-5/32 (29)

54 to 58

73.5 to 78.4

750 to 800

3-1. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)

2) Completely remove all burrs from the cut cross section of 

pipe. (Fig. 3)

•  Aim the copper pipe downward while removing burrs to 

prevent burrs from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, 

then put them on pipe having completed burr removal. 

(Not possible to put them on after flaring work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the 

dimension shown in the table. Select A inch (mm) from 

the table according to the tool selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section 

and do flaring work again.

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. 

(The stop valves are fully closed and covered in caps in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve 

on the side of the outdoor unit gas pipe.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)

4) Check the vacuum with gauge manifold valve, then close gauge manifold 

valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge manifold 

valve remains in the same position. Confirm that pressure gauge shows -14.7 

psi [Gauge] (-0.101 MPa).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Operating without 

fully opening lowers the performance and this causes trouble.

8) Refer to 1-2., and charge the prescribed amount of refrigerant if needed. Be 

sure to charge slowly with liquid refrigerant. Otherwise, composition of the 

refrigerant in the system may be changed and affect performance of the air 

conditioner.

9) Tighten cap of service port to obtain the initial status.

10

) Leak test

3.  FLARING WORK AND PIPE CONNECTION

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Stop valve 

for GAS

Stop valve cap

(Torque 19.6 to 

29.4 N•m, 200 

to 300 kgf•cm)

Gauge manifold 

valve (for R410A)

Compound pressure 

gauge (for R410A)

–0.101MPa  

(–760 mmHg)

Handle 

Low

Handle High

Vacuum pump

(for R410A)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Stop valve 

for LIQUID

Pressure gauge

(for R410A)

Precautions when us-

ing the control valve

When attaching the control valve 

to the service port, valve core may 

deform or loosen if excess pres-

sure is applied. This may cause 

gas leak.

Service port

Charge hose 

(for R410A)

Body

Close

Open

Control 

valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then tighten part A. Do not tighten 

part A or turn the body when valve 

core is in open position.

Service port cap

(Torque 13.7 to 

17.7 N•m, 

140 to 

180 kgf•

cm)

Charge hose 

(for R410A)

VG79A939H01_01En.indd   5

2018/08/03   15:53:02

Содержание Mitsubishi Electric NTXMMX20A122A Series

Страница 1: ...l installation de l appareil ext rieur Lors de l installation de l appareil int rieur consultez la notice d installation de cet appareil Toute alt ration structurelle requise pour l installation doit...

Страница 2: ...se parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could cause...

Страница 3: ...and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed with walls such as a verandah be sur...

Страница 4: ...meter or hard PVC pipe VP16 for drain socket 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 3 ft 1 m away from the TV antenna wire The Q ty for B to K in the abo...

Страница 5: ...AWG14 or stranded conductor Min AWG14 Use double insulated copper wire with 600 V insulation Use copper conductors only Follow local electrical code POWER SUPPLY CABLE Use solid or stranded conductor...

Страница 6: ...burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the tool se...

Страница 7: ...ping correction function This unit has a wiring piping correction function which corrects wiring and piping combination When there is possibility of incorrect wiring and piping combination and confirm...

Страница 8: ...manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection...

Страница 9: ...de la fiche d alimentation dans la prise secteur v rifiez qu aucune poussi re salet ni d l ment desserr n est pr sent sur la prise et la fiche Veillez enfoncer fond la fiche d alimentation dans la pr...

Страница 10: ...l unit externe Pour viter tout probl me de fonctionnement vitez d installer le climatiseur dans les endroits suivants En pr sence de fuites de gaz inflammable En pr sence d une grande quantit d huile...

Страница 11: ...pour l appareil int rieur Apr s le test de contr le des fuites appliquer soigneusement du mat riau isolant pour obstruer les trous Si la tuyauterie doit tre fix e sur un mur contenant des m taux de l...

Страница 12: ...ser des conducteurs en cuivre uniquement Respecter le code lectrique local AVERTISSEMENT Utiliser le c ble de connexion conforme aux normes techniques pour raccorder les unit s interne et externe et f...

Страница 13: ...l ouverture de service pour recr er les conditions d origine 10 Test de contr le des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile r frig rante G sur les embouts vas s des tuy...

Страница 14: ...et de c blage des appareils int rieurs ext rieurs Vous devez donc lancer les essais de fonctionnement l un apr s l autre Concernant le m canisme de protection contre une remise en marche trop rapide...

Страница 15: ...de l appareil int rieur pour la m thode d arr t du syst me Si trop de r frig rant a t ajout au syst me de climatisation il se peut que la pression ne parvienne pas baisser jusqu 0 1 0 psi jauge 0 05...

Страница 16: ...a toma podr a provocar incendios o descargas el ctricas Si el enchufe de alimentaci n presenta piezas sueltas sustit yalo Fije firmemente la cubierta de la instalaci n el ctrica a la unidad interior y...

Страница 17: ...el lado de salida de aire de la unidad exterior Para instalar el aparato de aire acondicionado evite los lugares siguientes donde es m s probable que ocurran problemas Donde pueda haber una fuga de ga...

Страница 18: ...3 15 16 pulg 100 mm M s de 7 7 8 pulg 200 mm si hay obst culos a ambos lados Despu s de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en...

Страница 19: ...de cobre Siga la normativa el ctrica local ATENCI N Conecte las unidades interior y exterior con el cable de conexi n norma lizado destinado a este fin y sujete bien el cable al panel de terminales de...

Страница 20: ...pa de la abertura de servicio de la v lvula de retenci n situada en el lado de la tuber a de gas de la unidad exterior Inicialmente las v lvulas de retenci n est n completamente cerradas y cubiertas c...

Страница 21: ...ger el acondicionador de aire Funci n de correcci n de conexiones tuber as Esta unidad tiene una funci n de correcci n de conexiones tuber as que corrige la combinaci n de las mismas Cuando exista la...

Страница 22: ...te el manual de instalaci n de la unidad interior para m s detalles acerca del m todo de detenci n de la operaci n Si se ha a adido demasiado refrigerante al sistema con acondicionador de aire puede q...

Страница 23: ...A4_white_tombo indd 1 2016 04 25 10 16 47...

Страница 24: ...G79A939H01 HEAD OFFICE 1340 SATELLITE BOULEVARD SUWANEE GA 30024 USA MITSUBISHI ELECTRIC TRANE HVAC US LLC VG79A939H01_cover4 indd 2 2018 08 03 11 27 51 Publication No DL SVN035A XX Published Dec 2018...

Отзывы: