Maintenance

Maintenance Contract
Training

It is strongly recommended that you
sign a maintenance contract with your
local Service Agency.  This contract
provides regular maintenance of your
installation by a specialist in our
equipment.
Regular maintenance ensures that any
malfunction is detected and corrected
in good time and minimizes the
possibility that serious damage will
occur.  Finally, regular maintenance
ensures the maximum operating life
of your equipment.  We would remind
you that failure to respect these
installation and maintenance
instructions might result in immediate
cancellation of the warranty.

The equipment described in this
manual is the result of many years of
research and continuous
development.
  To assist you in obtaining the best use
of it, and maintaining it in perfect
operating condition over a long period
of time, the constructor have at your
sisposal a refrigeration and air
conditioning service school.  The
principal aim of this is to give operators
and maintenance technicians a better
knowledge of the equipment they are
using, or that is under their charge.
  Emphasis is particularly given to the
importance of periodic checks on the
unit operating parameters as well as
on preventative maintenance, which
reduces the cost of owning the unit by
avoiding serious and costly
breakdown.

Fan Belt Maintenance

Clean fan belts and pulleys with a dry
cloth.  Oil and grease must be kept off
belts.  The use of a belt dressing is not
recommended.  When replacing belts,
use a matched set.  Do not force belts
onto pulleys, but adjust motor position
to allow mounting and then re-tighten.

Sheave (Pulley) Alignment

To prevent interference of the fan frame
with the belt, make sure that the belt
edge closest to the motor has the
proper clearance from the fan frame,
as shown in Figure 7.
Align the fan and motor sheaves by
using a straightedge as shown in
Figure 8.  The straightedge must be
long enough to span the distance
between the outside edges of the
sheaves.
When the sheaves are aligned, the
straightedge will touch both sheaves
at points A throught D.

CAUTION

!

DO NOT OVER-TENSION THE
BELTS. EXCESSIVE TENSION WILL
REDUCE FAN AND MOTOR
BEARING LIFE,ACCELERATE BELT
WEAR AND POSSIBLY CAUSE
SHAFT FAILURE. CLEAN THE
SHEAVES AND BELT WITH A DRY
CLOTH. OIL AND GREASE SHOULD
BE KEPT AWAY FROM THE BELT
BECAUSE THEY CAN CAUSE
DETERIORATION AND SLIPPAGE.
THE USE OF BELT DRESSING IS
NOT RECOMMENDED

Содержание LWHA

Страница 1: ...TRANE TRANE R Installation Operation Maintenance Belt Driven Direct Drive Low Height Air handler LWHA Model LWHA BC SVX002 E4 Sept 2011 ...

Страница 2: ...the carrier immediately by phone or any registered mail Notify the local Trane Sales Office Conceal damage must be reported within 15 days of delivery Check the unit nameplate to confirm that the proper unit was shipped Available power supply must be compatible with electrical characteristics specified on component nameplates Installation This manual covers the installation operation and maintenan...

Страница 3: ...TRANE Contents Model Nomenclature General Specification Unit Installation Dimension Data Electrical Wiring Diagram Operation Start Up Maintenance Trouble Analysis ii 1 2 3 4 5 8 9 12 13 14 15 17 18 20 ...

Страница 4: ... 22 23 24 25 26 27 28 29 30 X None For Direct Drive Code Dia KW A 11 0 18 B 14 0 37 C 19 0 75 D 24 1 1 1 5 E 28 2 2 3 G 90 N 132 X None A 63 H 95 O 140 B 67 I 100 P 150 C 71 J 106 Q 160 D 75 K 112 R 170 E 80 L 118 S 180 F 85 M 125 T 190 Model Belt Driven Direct Driven LWHA 013 LWHA 023 LWHA 033 LWHA 043 LWHA 053 LWHA 063 A 8 8 Single B 9 7 Single B 9 7 Single C 9 7 Twin D 10 8 Twin D 10 8 Twin E K...

Страница 5: ...e 1 Yes 0 Future Use 0 Future Use 0 Future Use Service Indicator E Revised Fan Model 2 LWHA Model Nomenclature Digit 15 Digit 16 Digit 17 Digit 18 19 20 21 Digit 22 Digit 23 Digit 24 Digit 25 Digit 26 Digit 27 Digit 28 Digit 29 Digit 30 A 1 A 1 2 0 0 4 X L 2 X 0 0 0 E L W H A 0 1 3 E A 2 A A A A A 1 A 1 2 0 0 4 X L 2 X 0 0 0 E 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27...

Страница 6: ... 18 0 37 0 75 0 7 1 2 2 0 2 5 5 0 10 4 254 10 787 4 31 0 2 2 15 LWHA 023 LWHA 033 LWHA 043 LWHA 053 LWHA 063 1750 2973 1118x523x1008 120 240x270 63 5 18 62 12 66 0 80 15 91 47 6 73 21 43 14 57 0 92 4 7 14 0 39 11 48 4 36 0 28 0 64 1 9 9 7 1750 0 37 0 75 1 1 1 2 2 0 2 5 5 0 10 4 14 6 355 6 14 914 4 36 0 33 3 5 2042 3469 1271x523x1008 130 240x270 76 22 24 15 12 0 95 24 22 72 4 88 5 25 95 17 64 1 11 ...

Страница 7: ...TRANE 4 General Specification LWHA 013 thru 063 EE ...

Страница 8: ...mounting lugs are provided at bottom of the unit The false ceiling opening must be large enough for future maintenance pan Refer to drain trap sketch in the piping section 4 Connect the ductwork to the unit Auxiliary Drain Pan A field fabricated auxiliary drain pan may be installed under the unit and when condensate overflow may cause damage This drain pan will eliminate any excess condensation th...

Страница 9: ...FIGURE 3 USE BACK UP WRENCH WHEN ATTACHING PIPING TO COILS ON THERADED CONNECTIONS Condensate Drain Con nections CAUTION FAILURE TO PROVIDE ADEQUATE CONDENSATE PIPING MAY RESULT IN WATER DAMAGE TO THE EQUIPMENT OR BUILDING DRAIN TRAPS MUST BE PRIMED IF THEY ARE NOT THE TRAP IS ESSEN TIALLY NON EXISTENT AND DRAIN PAN WILL LIKE OVERFLOW The threaded condensate drain connection is provided on the coi...

Страница 10: ...TRANE Unit Installation 7 ...

Страница 11: ...TRANE Unit Installation 8 ...

Страница 12: ...TRANE 9 Dimension Data Low Height Air Handling Unit Double Wall Direct Driven LWHA 013 023 LH Coil ...

Страница 13: ...TRANE 10 Dimension Data Low Height Air Handling Unit Double Wall Direct Driven LWHA 033 043 053 LH Coil ...

Страница 14: ...TRANE 11 Dimension Data Low Height Air Handling Unit Double Wall Belt Driven LWHA 013 023 033 LH Coil ...

Страница 15: ...TRANE 12 Dimension Data Low Height Air Handling Unit Double Wall Belt Driven LWHA 043 053 063 LH Coil ...

Страница 16: ...iring diagrams for LWHA Motors up to 2 2 kW or 3 0 HP are suitable for Direct On Line starting Larger Motors are suitable for both autotransformer and Star Delta starting Fan Motor Wiring Termination Three Terminal Fan Motor Wiring Termination Six Terminal ...

Страница 17: ... parallel j Check belt tension as per instruction given in the maintenance section Start Up procedures After completing all items under Pre Start Up the unit may be started and the following checks and adjustments performed a Bump start the motor to check the direction of rotation If the rotation need to be changed stop the motor completely and change the direction of rotation by changing the line...

Страница 18: ... thoroughly before re installing in the units Do not rub or wring Washable filters can also be cleaned by blowing with compressed air in opposite direction of filter airflow Fan Belt Tension Note Fan belt tension should be checked at least twice during the first day of operation since there is a rapid decrease in tension until belts are run in Proper belt tensioning is required to ensure maximum b...

Страница 19: ...TRANE 16 Maintenance Figure 6 Belt Tension Measurement Table1 Deflection Force K ...

Страница 20: ...sis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventative maintenance which reduces the cost of owning the unit by avoiding serious and costly breakdown Fan Belt Maintenance Clean fan belts and pulleys with a dry cloth Oil and grease must be kept off belts The use of a belt dressing is not recommended When replacing belts use a match...

Страница 21: ... DISCONNECT ELECTRICAL POWER SOURCE AND ALLOW ALL ROTATING EQUIPMENTTO STOP COMPLETELY BEFORE INSPECTING OR SERVICING THE UNIT FAILURE TO DO SO MAY RESULT IN PERSONAL INJURY OR DEATH FROM ELECTRICAL SHOCK OR MOVING PARTS WARNING DISCONNECT ELECTRICAL POWER PRIOR TO ACCESS INTO A FAN DUCTWORK EVEN WHEN LOCKED OUT ELECTRI CALLY FANS MAY CAUSE INJURY OR DAMAGE IF THE IMPELLER IS SUBJECT TO WINDMILLIN...

Страница 22: ...on Motor mounting bolts loose Worn motor bearings Fan rubbing on fan cover Recommended Action Adjust tension Replace bearing Correct alignment Check shaft level Replace fuse or reset circuit breaker Check and reset overload Check wiring with diagram supplied on unit Compare actual supply power with motor nameplate recommendations Contact power company for adjust ments Check that motor and driver r...

Страница 23: ...rk too short Drain pipe choked Improper or no U trap Water carry over due to high velocity Recommended Action Check belt tension and overhung load Replace sheave with larger one Adjust belt tension Replace belt or belt set Check sheave alignment Replace sheaves Replace sheaves Realign drive Check for leaky bearings Clean belts and sheaves Adjust tension Remove obstruction or realign drive for clea...

Страница 24: ...e has a policy of continuous product and product data improvement and reserves the right to charge design and specifications without notice Only qualified technicians should perform the installation and servicing of equipment referred to in this publication Trane www trane com For more information contact your local district office TRANE ...

Отзывы: