TRANE
®
14
Operation / Start-Up
Pre-Start-Up Inspection
Perform the following checks and
inspections before operating the unit.
Inspection Checklist
a)Unit is mounted securely to the
ceiling support rods (mounting
units).
b)Ductwork connections are
complete, valve and piping have
thoroughly insulated.
c)Coil connections are complete
and tight.
d)Condensate drain pan
connections are complete and
tight.
e)Electrical connections
completed. Wiring is correct and
in accordance with the wiring
diagram. Ground connection
completed.
f)Check and retighten, if necessary
all the motor, fan pulley, fan
bearings and wheel.
g)Rotate fan by hand, to ensure that
is runs freely and that there is no
interference.
h)Check and retighten, if
necessary, drive and bearing
bolts, motor clamp plate bolts
and isolator bolt.
i)Check to ensure that pulley is
correctly aligned and that shaft
is parallel.
j)Check belt tension as per
instruction given in the
maintenance section.
Start-Up procedures
After completing all items under "Pre-
Start-Up", the unit may be started and
the following checks and adjustments
performed:
a)Bump start the motor to check
the direction of rotation. If the
rotation need to be changed,
stop the motor completely and
change the direction of rotation
by changing the line connection.
b)After connecting the load, the
motor should start quickly and
run smoothly. If it does not, the
power supply should be
switched off at once and all
connections, as well as the
power supply, should be re-
checked before re-starting.
c)In the event of excessive vibration
or unusual noises, the motor
should be disconnected from the
load and checked for poor
alignment, loose mounting bolts,
etc.
d)When the motor has been
operated under load for a short
period of time, check that the
operating current with the
nameplate current.
e)Measure the motor voltage and
amps on all phases to insure
proper operation.
Compare these reading with the
motor nameplate
Содержание LWHA
Страница 7: ...TRANE 4 General Specification LWHA 013 thru 063 EE ...
Страница 10: ...TRANE Unit Installation 7 ...
Страница 11: ...TRANE Unit Installation 8 ...
Страница 12: ...TRANE 9 Dimension Data Low Height Air Handling Unit Double Wall Direct Driven LWHA 013 023 LH Coil ...
Страница 13: ...TRANE 10 Dimension Data Low Height Air Handling Unit Double Wall Direct Driven LWHA 033 043 053 LH Coil ...
Страница 14: ...TRANE 11 Dimension Data Low Height Air Handling Unit Double Wall Belt Driven LWHA 013 023 033 LH Coil ...
Страница 15: ...TRANE 12 Dimension Data Low Height Air Handling Unit Double Wall Belt Driven LWHA 043 053 063 LH Coil ...
Страница 19: ...TRANE 16 Maintenance Figure 6 Belt Tension Measurement Table1 Deflection Force K ...